Description
The HIMA F8627X is an Ethernet communication module for HIMA safety PLC systems like H41q and H51q, enabling safeethernet, Modbus TCP, OPC DA/A&E, and ELOP II TCP protocols for secure data exchange in process industries.

Product Parameters
- Power Supply: 5 VDC / 2 A via backplane.
- Interfaces: Two Ethernet ports, RS485 serial (isolated).
- Processor: Dual Intel 386EX 32-bit at 25 MHz.
- Memory: 1 MB Flash-EPROM (OS), 1 MB user program, 1 MB data SRAM.
- Bus Station: Ethernet 1-99, serial 1-31.
- Dimensions: 19-inch rack, 3 HU x 4 WU (about 140 x 20 mm).
Datasheet Summary
19-inch module plugs into safety PLC backplane for network connectivity up to 100 Mbps. Supports programming via ELOP II V4.1+, OPC servers, and Modbus slave modes with four-digit diagnostic display and safety watchdog output.
Origin
Germany (HIMA headquarters in Bruchsal).
Technical Details
Connects CPUs like F8650X/F8652X to Ethernet networks via backplane bus; handles safeethernet for redundancy and OPC for SCADA integration. Features galvanic isolation, short-circuit-proof 24V/500mA output, and fault-safe shutdown.
Common Q&A
- Compatible CPUs? F8650X, F8651X, F8652X, F8653X.
- Protocols supported? Safeethernet, Modbus TCP slave, OPC DA/A&E, ELOP II TCP.
- Diagnostic features? 4-digit matrix display, LEDs.
- Power draw? 10 W max from 5V bus.
- Mounting? 19-inch rack slot.
Similar Models
| Model | Key Features |
|---|---|
| F8627 | Legacy Ethernet version |
| F8628X | Profibus DP slave alt. |
| F8621A | Basic serial comms |
| F8620 | Modbus RTU module |
| F8650X | Paired safe CPU |
| F7133 | Digital I/O companion |
| F8628 | Profibus standard |
| F8671A | Relay output match |