Description
Product Overview
The HIMA HIMatrix F60 DIO 24/16 01 is a digital input/output module for the modular F60 HIMatrix safety controller. It provides 24 digital input channels and 16 digital output channels, with the I/O channels galvanically separated from the I/O bus. LEDs on the front panel provide visual indication of input and output status.
The module is intended for safety-related automation applications where field signals need to be monitored and controlled by the HIMatrix F60 system. HIMA documentation identifies the F60 DIO 24/16 01 for applications up to SIL 3, Category 4 and PL e, with additional certification information depending on the applicable standard.
The module can be installed in F60 subrack slots 3 through 8. Slots 1 and 2 are reserved for the power supply and central module respectively.

Key Features
- 24 digital input channels
- 16 digital output channels
- Galvanic separation between I/O channels and the I/O bus
- Front-panel LED indication for I/O status
- Designed for HIMA HIMatrix F60 modular systems
- Safety-related digital inputs and outputs
- Configurable line monitoring
- Suitable for monitoring short circuits and open circuits in appropriate safety applications
- Compatible with HIMA safety-system engineering tools according to firmware/system revision
- Certified for safety-related applications up to SIL 3 / Cat. 4 / PL e under the applicable standards
Technical Datasheet
| Parameter | Specification |
|---|---|
| Brand | HIMA |
| Product Family | HIMatrix |
| Model | F60 DIO 24/16 01 |
| Product Type | Digital Input/Output Module |
| System | HIMatrix F60 |
| Digital Inputs | 24 |
| Digital Outputs | 16 |
| I/O Isolation | Galvanically separated from I/O bus |
| Nominal Supply | 24 VDC |
| Supply Range | 20.4–28.8 VDC |
| Installation | F60 modular subrack |
| Supported Slots | Slots 3–8 |
| Input/Output Status | Front-panel LEDs |
| Safety Application | Up to SIL 3 / Cat. 4 / PL e, depending on applicable standard |
| Hazardous-Area Suitability | Zone 2 installation possible subject to specified conditions |
| Maximum Ambient Temperature | Up to 60°C for the referenced certification configuration |
| Configuration Tools | SILworX / ELOP II Factory, depending on CPU operating-system revision |
HIMA’s certification documentation gives a rated voltage of 20.4–28.8 V and lists the F60 DIO 24/16 01 among the HIMatrix devices covered by the relevant certification.
Digital Input and Output Functions
The 24 inputs are arranged as safety-related digital inputs. HIMA documentation describes common short-circuit-protected supply arrangements for groups of eight inputs.
The 16 digital outputs provide the interface between the F60 central processing system and connected actuators. The first eight outputs can also be used for line-control functions in suitable safety circuits.
For example, pulsed outputs can be connected to digital inputs to help detect conditions such as open circuits, cross-circuits, incorrect wiring, or certain earth faults. This function can be useful for safety-related emergency-stop monitoring.
Typical Applications
The F60 DIO 24/16 01 is suitable for existing HIMatrix F60 safety-control installations such as:
- Emergency-stop monitoring
- Safety interlock systems
- Burner and boiler control
- Process safety systems
- Machine safety applications
- Industrial shutdown systems
- Digital sensor monitoring
- Safety actuator control
- Industrial automation systems requiring safety-related I/O
The exact safety function must always be engineered and validated according to the applicable safety standards and the complete system configuration.
Installation & Configuration
Before replacing or installing the module, verify the F60 system configuration and the firmware/tool version.
Recommended procedure:
- Confirm the complete part number and module identification.
- Record the existing slot position and wiring.
- De-energize the system according to the approved maintenance procedure.
- Observe appropriate ESD precautions when handling the module.
- Install the module in an F60 I/O slot, positions 3–8.
- Check the terminal plugs and field wiring.
- Restore the 24 VDC supply.
- Check the front-panel LED indications.
- Configure the module using the appropriate HIMA engineering software.
- Verify all digital input and output functions.
- Perform the required safety-function tests before returning the system to operation.
HIMA documentation states that SILworX is required for CPU operating-system version 7 and higher, while ELOP II Factory is used with CPU operating systems up to V6.x.
Maintenance & Inspection
For a replacement or spare module, inspect:
- Front-panel condition
- LED indicators
- Terminal connectors
- Connector contacts
- Module housing
- Part-number label
- Signs of corrosion or moisture
- Evidence of overheating
- PCB or enclosure damage
- Correct firmware/system compatibility
During commissioning, verify every connected input and output individually rather than relying only on the absence of a module fault.
Particular attention should be paid to safety-related wiring. HIMA documentation notes that residual risks can result from engineering, user-program, or wiring faults, so the module should not be treated as an independent safety device.
Zone 2 Installation
The F60 DIO 24/16 01 has documentation covering Zone 2 installation under specified conditions. For such installations, HIMA requires an appropriate enclosure meeting the applicable protection requirements and a suitably isolated 24 VDC supply.
The documentation specifies that the F60 DIO 24/16 01 can dissipate up to 25 W at maximum output load, which must be considered when designing the enclosure and thermal management.
Do not use the Zone 2 information as a blanket approval for every installation. The actual module marking, certificate, enclosure, ambient temperature and complete installation must be checked.
Replacement Notes
When purchasing a replacement, match the exact designation:
HIMA HIMatrix F60 DIO 24/16 01
Do not confuse it with other F60 modules such as:
- F60 DI 32 01 — 32-channel digital input module
- F60 DO 8 01 — 8-channel relay output module
- F60 MI 24 01 — 24-channel analog/proximity input module
- F60 DIO 16/8 01 — different digital I/O configuration
HIMA’s certification documentation separately identifies these module types, confirming that the DIO 24/16 01 should be matched by its complete model designation rather than simply by the F60 family name.
For an existing system, also verify the firmware revision, configuration file, slot position, terminal wiring and safety application before commissioning.
Identification Information
| Identification | Value |
|---|---|
| Manufacturer | HIMA Paul Hildebrandt GmbH |
| Family | HIMatrix |
| Controller | F60 |
| Module | DIO 24/16 01 |
| Function | Digital Input / Digital Output |
| I/O Count | 24 DI / 16 DO |
| Supply | 24 VDC |
| Safety Class | Up to SIL 3 / Cat. 4 / PL e under applicable certification |
The current eBay listing identifies the item as a HIMA HIMatrix F60 DIO 24/16 01 input/output module. The listing condition is “New: Other” and the seller describes it as being “In the box.”
Recommended eBay SEO Title
HIMA HIMatrix F60 DIO 24/16 01 | 24DI 16DO Safety Digital I/O Module