Description
Product Overview
The HIMA HIMatrix F60 PS 01 is the dedicated power supply module for the modular HIMatrix F60 safety controller system.
The PS 01 supplies the required operating voltages for the F60 programmable electronic system and provides galvanically isolated voltage outputs. It is designed specifically for the F60 architecture and can only be installed in the first slot of the F60 subrack.
The module also monitors its output voltages. If an output voltage becomes too high, the power supply module switches off to protect the system. Front-panel LEDs provide status indication for service and diagnostics.

Technical Specifications
| Parameter | Specification |
|---|---|
| Brand | HIMA |
| Product Family | HIMatrix F60 |
| Model | PS 01 / PSU 01 |
| Module Type | Power Supply Module |
| HIMA Part No. | 98 220096 |
| Installation Position | Slot 1 |
| Input Supply | 24 VDC system supply |
| System Supply Range | 20.4–28.8 VDC nominal operating range |
| Voltage Isolation | Galvanically isolated internal voltages |
| Status Indication | Front-panel LEDs |
| Safety Application | SIL 3 / Cat. 4 / PL e; applicable certifications also cover SIL 4 railway applications |
| System | HIMatrix F60 Modular Safety Controller |
HIMA’s PS 01 manual identifies the module part number as 98 220096. The F60 system documentation specifies a nominal 24 VDC supply with a -15% to +20% range, corresponding to 20.4–28.8 VDC.
Main Functions
The PS 01 performs several important functions within the F60 system:
- Supplies the F60 programmable electronic system
- Generates the required internal operating voltages
- Provides galvanic separation between the relevant supply voltages
- Monitors output-voltage conditions
- Switches off when an excessive output voltage is detected
- Provides front-panel status indication
- Supports the safety-related power architecture of the HIMatrix F60
Unlike a general-purpose 24 VDC power supply, the PS 01 is a dedicated F60 system module and should be matched to the correct HIMA hardware configuration.
HIMatrix F60 System Position
The F60 rack has dedicated positions for its power supply and central processing hardware.
| F60 Slot | Module |
|---|---|
| Slot 1 | PS 01 Power Supply Module |
| Slot 2 | CPU / Central Module |
| Slots 3–8 | I/O Modules |
The PS 01 is not configured as a normal I/O module in SILworX or ELOP II Factory. It occupies the first slot, while the central module is installed in Slot 2 and the application I/O modules occupy Slots 3 through 8.
Typical Applications
The PS 01 is used as part of HIMatrix F60 safety controller installations in applications such as:
- Industrial safety systems
- Emergency shutdown systems
- Process safety applications
- Burner and boiler protection
- Machinery safety
- Power generation
- Oil and gas automation
- Railway and transportation safety systems
The module is part of the certified F60 safety-system architecture rather than an independent field power supply. HIMA documentation lists the PS 01 within the HIMatrix F60 safety-related system.
Installation & Configuration
The PS 01 is mechanically and electrically specific to the F60 system.
Before replacement:
- Place the safety system in the appropriate maintenance state.
- Remove system power according to the applicable site procedure.
- Verify the PS 01 part number and hardware revision.
- Confirm that the module is being installed in F60 Slot 1.
- Inspect the backplane connector and module interface.
- Check the incoming 24 VDC supply and external protection.
- Install the PS 01 securely in the rack.
- Restore power and check the front-panel LEDs.
- Verify the F60 CPU and I/O modules reach their expected operating states.
The PS 01 itself is not configured through the normal I/O configuration process. HIMA documentation specifically identifies it as the F60 power supply module occupying Slot 1.
Inspection & Maintenance
For spare-parts inventory or replacement work, inspect the following:
- HIMA model marking
- Part number
- Hardware revision
- Firmware revision where shown
- Operating-voltage marking
- Front-panel LEDs
- Backplane connector
- Housing and mounting hardware
- Signs of corrosion, contamination, or overheating
HIMA’s PS 01 documentation states that the type label includes the product name, barcode, part number, production year, hardware revision, firmware revision, operating voltage, and conformity markings.
For a replacement unit, a basic functional check should include power-up, output-voltage monitoring, LED status verification, and confirmation that the F60 controller starts normally.
Compatibility Notes
The key identification is:
PS 01 = HIMatrix F60 Power Supply Module
It should not be confused with:
- F60 CPU 01 — Central Module
- F60 CPU 03 — Central Module
- AI 8 01 — Analog Input Module
- AO 8 01 — Analog Output Module
- DO 8 01 — Digital Output Module
- DI 32 01 — Digital Input Module
There is also a PS 014 variant. HIMA documentation identifies PS 014 as a different power supply version intended for an extended operating-temperature range and additional railway-related environmental testing. Therefore, PS 01 and PS 014 should not be treated as automatically interchangeable.
Condition
The referenced eBay listing is for a HIMA HIMatrix F60 PSU01 / PS 01 power module.
Before shipment, it is recommended to verify the physical nameplate, part number, hardware revision, connector condition, and packaging against the buyer’s existing F60 system.
Ordering Information
For replacement inquiries, provide the complete identification from the module label:
- HIMatrix F60
- PS 01 / PSU 01
- Part number
- Hardware revision
- Quantity required
A clear photograph of the module nameplate is especially useful when distinguishing PS 01 from PS 014 or other F60 hardware revisions.
Recommended eBay Title