The ESSER by Honeywell 808610.10B is an Esserbus 12 Relay Transponder designed for fire alarm and fire detection control systems. It operates as a loop device and provides decentralized relay outputs for expanding the control capability of a compatible ESSER fire alarm control panel.
The module provides 12 relay outputs. Eleven relays can be programmed individually for different switching functions, while the remaining relay is assigned to a system-related function. Depending on the operating configuration, the relay contacts can be used in potential-free operation or with an external switching voltage.
The transponder is powered through the multifunctional Esserbus primary line and can be integrated into compatible fire detection systems. An optional loop isolator PCB can also be used where required by the installation design.

⚙️ Main Features
🔹 ESSER by Honeywell fire alarm system component
🔹 Model 808610.10B
🔹 Related standard part identification: 808610.10
🔹 Esserbus decentralized relay transponder
🔹 12 relay outputs
🔹 11 freely programmable relays
🔹 One loop address required per transponder
🔹 Loop-powered communication and control electronics
🔹 External relay switching supply supported
🔹 12 VDC or 24 VDC external switching voltage capability
🔹 Maximum relay contact load of 30 VDC / 1 A
🔹 Maximum combined relay load of 3 A per transponder
🔹 Optional loop isolator compatibility
🔹 Compact PCB module design
🔹 Suitable for fire alarm control and external equipment switching
📋 Product Datasheet
🔹 Brand: ESSER by Honeywell
🔹 Model: 808610.10B
🔹 Related Part Number: 808610.10
🔹 Series: Esserbus
🔹 Product Name: 12 Relay Transponder
🔹 Product Type: Fire Alarm Relay Output Module
🔹 Main Function: Decentralized Relay Output Expansion
🔹 Number of Relays: 12
🔹 Programmable Relays: 11 freely programmable outputs
🔹 Loop Address Requirement: 1 address per transponder
🔹 Operating Voltage: 10 to 28 VDC
🔹 External Relay Switching Supply: 12 VDC or 24 VDC
🔹 Relay Contact Load: 30 VDC / 1 A
🔹 Maximum Combined Load: 3 A per transponder
🔹 Quiescent Current: Approximately 250 µA at 19 VDC
🔹 Current Consumption: Approximately 3 mA at 12 VDC
🔹 Maximum External Device Cable Length: Up to 1000 m
🔹 Operating Temperature: -10°C to +50°C
🔹 Storage Temperature: -25°C to +75°C
🔹 Maximum Humidity: Below 95%
🔹 Protection Rating: IP40 when installed in a suitable housing
🔹 Dimensions: Approximately 150 × 82 × 20 mm
🔹 Weight: Approximately 110 g
🔹 Optional Accessory: 788612 Loop Isolator PCB
🔹 Approvals: VdS and BOSEC are listed for the 808610.10 product version
🔹 Country of Origin: Verify from the physical product label
🔹 Product Status: Fire alarm system spare part
🔹 Condition: New Surplus, subject to actual inventory condition
The manufacturer identifies 808610.10 as an Esserbus transponder with 12 relays, 11 freely programmable relay functions, a 10 to 28 VDC operating range, and a relay contact rating of 30 VDC / 1 A.
🔥 Fire Alarm System Function
The 808610.10B is designed to expand the number of relay-controlled outputs available within a compatible fire alarm control system.
Typical relay-controlled equipment may include:
🔹 Fire dampers
🔹 Smoke control equipment
🔹 External signaling devices
🔹 Building control interfaces
🔹 Shutdown circuits
🔹 Ventilation control interfaces
🔹 Auxiliary alarm equipment
🔹 External monitoring systems
🔹 Industrial fire protection equipment
The exact switching function of each relay depends on the programming and configuration of the fire alarm control system.
🔌 Esserbus Loop Integration
The transponder operates as a device on the Esserbus multifunctional primary line.
A major advantage of the module is that only one loop address is required for the complete transponder. The system can support multiple transponders according to the capacity and configuration of the connected fire alarm control panel.
Manufacturer information for the 808610.10 identifies limits of up to 100 transponders per compatible fire alarm control panel and up to 32 transponders per loop or detector zone, depending on the system configuration.
⚡ Relay Output Configuration
The module provides twelve relay outputs.
Eleven relay outputs can be programmed individually for different control functions.
The relay contacts can be configured according to the application requirements and supported operating mode.
The transponder can operate with an external switching voltage for relay operation. Supported external supply configurations include:
🔹 12 VDC
🔹 24 VDC
In potential-free operating configurations, an external relay switching voltage may not be required for the applicable programmable relay outputs.
The maximum contact load is rated at:
30 VDC / 1 A per relay contact
The combined load must not exceed:
3 A per transponder
These electrical limits should be observed when connecting external equipment.
🏭 Typical Applications
The ESSER by Honeywell 808610.10B can be used in compatible fire detection and fire alarm installations requiring additional decentralized relay outputs.
Typical applications include:
🔹 Commercial building fire alarm systems
🔹 Industrial facilities
🔹 Manufacturing plants
🔹 Power facilities
🔹 Data centers
🔹 Transportation infrastructure
🔹 Large building automation systems
🔹 Fire protection control panels
🔹 Smoke extraction interfaces
🔹 HVAC shutdown systems
🔹 Fire damper control interfaces
🔹 External alarm and status signaling
🛠 Installation and Replacement Guide
1. Verify the complete identification
Check the installed module carefully before replacement.
Compare:
🔹 808610.10B marking
🔹 Related 808610.10 identification
🔹 Hardware revision
🔹 Relay configuration
🔹 Terminal arrangement
🔹 Installed fire alarm system
A physical comparison of the original module is recommended before installation.
2. Isolate the fire alarm system correctly
Fire alarm equipment should only be serviced according to the approved maintenance procedure.
Notify responsible personnel and follow the applicable fire protection and system isolation requirements before disconnecting any equipment.
3. Record the wiring
Before removing the existing module, record:
🔹 Loop wiring
🔹 Relay output wiring
🔹 External power supply wiring
🔹 Terminal numbers
🔹 Connected external devices
🔹 Existing programming configuration
4. Check the external relay supply
If the installation uses an external switching voltage, verify the correct supply level before connecting the replacement module.
Supported relay switching configurations may include:
🔹 12 VDC
🔹 24 VDC
5. Install the module
Connect the module according to the original system wiring and approved ESSER installation documentation.
Avoid forcing terminal blocks or connectors.
6. Perform functional testing
After installation, verify:
🔹 Loop communication
🔹 Device recognition
🔹 Relay switching
🔹 External equipment response
🔹 Fault monitoring
🔹 Alarm functions
🔹 Fire alarm control panel diagnostics
Fire alarm control equipment should be commissioned and tested by qualified personnel.
🔄 Compatibility Notes
The 808610.10B should be selected according to the complete product identification and the installed ESSER fire alarm system.
Before replacement, verify:
🔹 Exact part number
🔹 Hardware revision
🔹 Esserbus compatibility
🔹 Fire alarm control panel type
🔹 Loop configuration
🔹 Relay programming
🔹 External switching voltage
🔹 Terminal arrangement
🔹 Connected field equipment
Do not assume that another Esserbus transponder with a similar physical appearance provides the same relay functions.
❓ Frequently Asked Questions
Q1: What is the ESSER by Honeywell 808610.10B?
It is an Esserbus fire alarm transponder designed to provide 12 relay outputs for compatible ESSER fire detection and fire alarm systems.
Q2: How many relay outputs does it provide?
The module provides 12 relays. Eleven of the relays are freely programmable for supported system functions.
Q3: Does the module require its own loop address for every relay?
No. The complete transponder requires only one loop address.
Q4: What operating voltage does the module use?
The listed operating voltage range is 10 to 28 VDC.
Q5: Can the relay outputs use an external power supply?
Yes. The relay switching configuration can use an external 12 VDC or 24 VDC supply, depending on the installation and operating mode.
Q6: What is the relay contact rating?
The maximum relay contact load is 30 VDC / 1 A, with a combined maximum load of 3 A per transponder.
Q7: What are the dimensions?
The module dimensions are approximately 150 × 82 × 20 mm.
Q8: What is the approximate weight?
The listed weight is approximately 110 g.
Q9: Can an isolator be added?
Yes. The 788612 loop isolator PCB is listed as an optional accessory for the transponder.
Q10: Can this module be used as a general industrial PLC relay card?
No. It is a system-specific Esserbus module designed for compatible fire alarm and fire detection control systems.
⭐ Recommended ESSER by Honeywell Models
🔹 ESSER by Honeywell 808610.10 – Esserbus 12 Relay Transponder
🔹 ESSER by Honeywell 808611.10 – Esserbus 32 LED Transponder
🔹 ESSER by Honeywell 808613.30 – Esserbus SIE Transponder for Third-Party Extinguishing Panels
🔹 ESSER by Honeywell 808619.10 – Esserbus FSA Transponder for Fire Doors
🔹 ESSER by Honeywell 808623 – Esserbus Alarm Transponder
🔹 ESSER by Honeywell 808623.40 – Esserbus Transponder for Special Detectors
🔹 ESSER by Honeywell 808606 – IQ8FCT XS Esserbus Transponder
🔹 ESSER by Honeywell 808621 – IQ8FCT LP Esserbus Transponder
🔹 ESSER by Honeywell 808630.10 – Esserbus RZT 24 V Transponder
🔹 ESSER by Honeywell 808631.10 – Esserbus RZT 12 V Transponder
These models belong to the ESSER Esserbus transponder range, but they perform different input, output, alarm, detector, and fire-control functions. Exact compatibility should be confirmed before selecting a replacement.
🔍 Inspection Before Shipment
For a New Surplus ESSER by Honeywell 808610.10B module, recommended inspection includes:
🔹 Verify the complete product identification
🔹 Check the relay components
🔹 Inspect terminal blocks
🔹 Check PCB traces
🔹 Inspect solder joints
🔹 Check for corrosion
🔹 Inspect for physical damage
🔹 Verify connector and terminal positions
🔹 Record hardware markings
🔹 Perform suitable power and communication checks where compatible test equipment is available
🔹 Verify relay operation when safe test conditions are available
🔹 Package using ESD-safe protective materials
📌 Product Identification
Brand: ESSER by Honeywell
Model: 808610.10B
Product Name: Esserbus 12 Relay Transponder
Series: Esserbus
Product Type: Fire Alarm Relay Output Module
Relay Outputs: 12
Programmable Relays: 11
Operating Voltage: 10–28 VDC
External Relay Supply: 12 VDC or 24 VDC
Relay Contact Rating: 30 VDC / 1 A
Maximum Combined Relay Load: 3 A per transponder
Dimensions: 150 × 82 × 20 mm
Weight: Approximately 110 g
Application: ESSER Fire Alarm and Fire Detection Systems