Description
The Kongsberg RDi-32A is a high-density Remote Analog Input Module designed for demanding marine and industrial automation infrastructures. This module serves as a robust acquisition interface, capable of monitoring up to 32 independent analog field signals simultaneously. Engineered by Kongsberg Maritime, it features high galvanic isolation and exceptional signal filtering, converting sensitive analog metrics from cargo tanks, engine components, and machinery spaces into secure digital telemetry for the master control network.
⚙️ Technical Parameters & Specifications
- Model Number: RDi-32A
- Device Type: 32-Channel Remote Analog Input Module
- Input Channel Capacity: 32 Channels (Configurable for voltage or current loops)
- Signal Ranges: Standard industrial ranges (e.g., 4-20mA, 0-20mA, 0-10V DC)
- Dimensions: 165 mm x 120 mm x 65 mm
- Weight: 0.78 kg
- Country of Origin: Norway
🚀 Application Areas
- Integrated Automation Systems (IAS): Gathering complex sensor variables from shipboard auxiliary systems.
- Cargo Monitoring Networks: Processing level, pressure, and temperature transmitter signals from multi-tank storage configurations.
- Propulsion Plant Telemetry: Interfacing temperature and fluid pressure monitors on main diesel engine frames.
- Decentralized Control Panels: Providing concentrated I/O pooling inside machinery spaces to reduce hardwired cable runs.
📖 Product Usage Instructions
The RDi-32A module is designed to snap securely onto standard TS35 DIN rails within a localized field termination enclosure. Ensure proper ventilation spaces are left clear around the module housing to facilitate convection cooling. All analog instrumentation lines must be routed using twisted, shielded pairs, with the cable shields tied to a clean instrumentation ground bar at the cabinet entry point. Disconnect the auxiliary power supply before plugging or unplugging the terminal blocks to shield internal converter circuits from transient voltage spikes.
🌐 Communication Configuration Steps
- IP Address / Fieldbus Setup: Connect the module to the engineering laptop running the Kongsberg system configuration utility. Assign a dedicated static IP address and corresponding subnet mask within the architecture of the vessel’s process control network.
- Station Number: Assign a unique station ID or node index using the software configuration panel or the physical address dip-switches located beneath the protective front cover plate.
- Baud Rate / Network Speed: Configure the communication ports to align with the dual-redundant system network. The internal fieldbus interfaces typically synchronize automatically to 10/100 Mbps on Ethernet lines or up to 1 Mbps on dedicated CAN bus segments.

⚡ Power-Up & Commissioning Flow
- Loop Integration Check: Visually audit all 32 channel terminal blocks to verify correct polarity mapping and ensure no stray wire strands cause short circuits.
- Power Feeder Audit: Measure the auxiliary power terminals to confirm the presence of a stable, noise-free 24V DC nominal input supply.
- Module Initialization: Switch on the cabinet power circuit breaker. The module’s power LED will turn green, and the status indicators will cycle as the internal firmware boots up.
- Channel Signal Validation: Apply a simulated 4-20mA signal to Channel 1 using a current calibrator and verify that the corresponding telemetry register registers the accurate percentage value on the master HMI console.
✅ Initial Operation Checklist
- Is the module’s DIN-rail metal grounding spring clip firmly tracking on a bonded backplane?
- Have individual channel configuration profiles been matched to their physical sensor types (e.g., current vs. voltage input mode)?
- Are the primary and secondary network cables securely connected to ensure communication redundancy?
- Does the master display register an open-circuit error code when a loop wire is intentionally disconnected for testing?
❓ Common Questions (Q&A)
Q: What does a flashing red status LED indicate on a specific channel sector?
A: A blinking red indicator points to an active channel loop fault. This typically means the connected sensor is experiencing a line break (open circuit), a short circuit, or the input signal has exceeded the maximum allowable out-of-range safety threshold.
Q: Can this module accept direct connections from Pt100 RTD temperature sensors?
A: The RDi-32A is optimized for standard analog process signals like 4-20mA or 0-10V. To interface raw RTD or thermocouple elements, you will need to pass the signals through external signal converters or utilize an RDi-series module specifically designated for temperature inputs.
Q: Is the RDi-32A hot-swappable during system operation?
A: While the network protocol allows for online module discovery, it is highly recommended to isolate the 24V DC auxiliary power feed before physically replacing the module unit to prevent field wiring ground faults or accidental short circuits on neighboring components.