Description
Product Technical Parameters
| Feature | Specification |
|---|---|
| Brand | SIEMENS |
| Model | 6DL1134-6TH00-0PH1 |
| Series | SIMATIC ET 200SP HA |
| Module Type | Analog Input Module (AI 16xI 2-wire HART) |
| Number of Channels | 16 Channels |
| Signal Type | 4 mA to 20 mA (Current) |
| Protocol Support | HART (Highway Addressable Remote Transducer) |
| Resolution | 16-bit including sign |
| Redundancy | Supports Terminal Block Redundancy |
Product Datasheet
| Attribute | Details |
|---|---|
| Dimensions | 22.5 mm x 115 mm x 75 mm |
| Weight | 0.16 kg (approx. 0.35 lbs) |
| Country of Origin | Germany |
| Power Supply | 24 VDC |
| Isolation | Tested with 707 VDC (Type Test) |
| Power Loss | 1.8 W (Typical) |
| Protection Class | IP20 |
Application Fields
The 6DL1134-6TH00-0PH1 is specifically designed for high-availability process automation environments. Key applications include:
- Chemical and Petrochemical Processing
- Water and Wastewater Management
- Oil and Gas Extraction and Refining
- Pharmaceutical Manufacturing
- Distributed Control Systems (DCS) requiring HART field device integration

Product Instructions
- Installation: Mount the module onto the appropriate ET 200SP HA carrier module. Ensure the module is firmly clicked into place to establish a secure connection with the backplane bus.
- Wiring: Connect 2-wire current transducers to the terminal block. The module provides the supply voltage for the sensors. Ensure polarity is correct to prevent measurement errors.
- Configuration: Use TIA Portal or SIMATIC PCS 7 to configure the hardware. Enable HART communication in the software parameters if digital field device data (like secondary variables or diagnostics) is required.
- Maintenance: The module supports “Hot Swapping,” allowing for replacement during operation if the station is configured for such action. Always verify the status LEDs (DIAG, MT) before removal.
Product Q&A
Q: Does this module support 4-wire transducers? A: This specific model is optimized for 2-wire current transducers where the module provides the loop power. For 4-wire configurations, an external power supply or a different module variant may be required.
Q: What is the benefit of the “HART” capability in this module? A: HART allows the module to transmit and receive digital information over the analog 4-20mA signal, enabling remote configuration, advanced diagnostics, and additional process variables from the field device.
Q: Can this module be used in a redundant configuration? A: Yes, it is designed for the ET 200SP HA system, which supports high-availability redundant configurations when used with the appropriate redundant terminal blocks and carrier modules.
Q: What do the LED indicators on the front panel signify? A: The ‘DIAG’ LED indicates the general module status (green for OK, red for fault), while channel-specific LEDs indicate the status of each individual input (e.g., wire break or overflow).
Similar Models Recommendation
- SIEMENS 6DL1134-6JH00-0PH1
- SIEMENS 6DL1135-6TF00-0PH1
- SIEMENS 6ES7134-6GD01-0BA1
- SIEMENS 6ES7134-6HD01-0BA1
- SIEMENS 6DL1131-6BL00-0PH1