Description
Product Description
The TRICONEX 3806E is an eight-channel Triple Modular Redundant (TMR) analog output module designed for Tricon safety and process control systems. It provides six standard 4–20 mA output channels and two dedicated high-current 20–320 mA channels, making it suitable for conventional analog control signals as well as high-current actuator and servo-valve applications. The module receives output commands from the three main processor channels, performs hardware voting, and uses a healthy channel to drive the field outputs. Internal current-loop feedback and voltage-reference monitoring support output verification, self-calibration, and module diagnostics. The 3806E is particularly relevant to turbomachinery and other applications requiring high-current control signals. It connects to the Tricon system through a compatible chassis and external termination panel (ETP). Before installation or replacement, verify the ETP model, field wiring, external loop power, output load requirements, and Tricon system revision. The 3806E should not be treated as a direct substitute for the standard 3805E or bipolar 3807 module because their output ranges and field-interface requirements differ.

TRICONEX 3806E
Product Datasheet
| Parameter | Specification |
|---|---|
| Brand | TRICONEX |
| Model | 3806E |
| Series | Tricon v9–v11 |
| Product Name | TMR Analog Output Module |
| Product Type | High-current analog output module |
| Architecture | Triple Modular Redundancy (TMR) |
| Number of Output Channels | 8 |
| Standard Analog Outputs | 6 channels, 4–20 mA |
| High-Current Outputs | 2 channels, 20–320 mA |
| Output Points | Points 2–4 and 6–8: 4–20 mA; Points 1 and 5: 20–320 mA |
| Resolution | 12 bits |
| Output Overrange | Approximately +6%; up to 21.2 mA and 339.2 mA respectively |
| Standard Output Accuracy | Less than 0.25% of full-scale range under specified operating conditions |
| High-Current Output Accuracy | Less than 0.25% of full-scale range under specified operating conditions |
| Output Coupling | DC-coupled |
| Output Isolation | Outputs are not individually isolated; commoned return |
| Recommended Loop Supply | 24–32 V DC, 3 A minimum |
| Extended Loop Supply Range | 20–36 V DC, 3 A minimum |
| Maximum Continuous Overvoltage | Below 42.5 V DC |
| Standard Output Load | Up to 825 Ω at 32 V DC, depending on loop supply |
| High-Current Output Load | Up to 50 Ω at 32 V DC, depending on loop supply |
| External Loop Power | 24 V DC nominal, reverse-voltage protected |
| Diagnostic Functions | Output-current feedback, loop monitoring, internal reference monitoring, and channel diagnostics |
| Front-Panel Indicators | PASS, FAULT, ACTIVE, LOAD, PWR1, PWR2 |
| Color Code | Light green |
| Installation | Tricon compatible chassis with external termination panel |
| Engineering Software | TriStation, subject to system version |
| Dimensions | Not independently verified |
| Weight | Not independently verified |
| Country of Origin | USA reported by suppliers; individual unit origin not verified |
| Product Status | Legacy industrial control spare |
| Discontinued | Current manufacturer lifecycle status not verified |
First-Time Operation Inspection Checklist
- 🔍 Model verification: Confirm the module label reads 3806E. Do not confuse it with 3805E, 3805H, or 3807.
- 🧩 System compatibility: Verify the Tricon chassis generation, system revision, and configured I/O allocation.
- 🔌 ETP inspection: Confirm the external termination panel and cable assembly are compatible with the 3806E.
- ⚡ Loop power: Verify the external 24–32 V DC supply arrangement and available current capacity.
- 📐 Channel assignment: Identify the six 4–20 mA channels and the two high-current channels at points 1 and 5.
- 🔧 Load verification: Check actuator, servo-valve, and field-device impedance against the permitted load at the actual loop voltage.
- 🔄 Wiring inspection: Verify common returns, polarity, terminal assignments, cable condition, and grounding.
- 🧪 Output testing: Test each output using an appropriate calibrated current-measurement instrument and an approved test procedure.
- 🛡️ TMR diagnostics: Confirm processor-channel status, module health, output feedback, and fault indications before returning the system to service.
Daily Maintenance
- 📊 Review analog output values against the control-system demand and field-device response.
- 🔍 Monitor PASS, FAULT, ACTIVE, LOAD, PWR1, and PWR2 indicators.
- ⚡ Check external loop-power stability and investigate undervoltage or overvoltage conditions.
- 🔌 Inspect termination-panel connections for loose terminals, corrosion, and overheating.
- 🧰 Check high-current actuator circuits for abnormal heating, excessive load, or unstable current.
- 🔄 Compare output commands with measured feedback to identify wiring or field-device problems.
- 📝 Record channel faults, output deviations, maintenance work, and configuration changes.
- 📋 Perform periodic channel calibration and proof testing according to the site’s approved maintenance schedule.
Troubleshooting and Frequently Asked Questions
Q1: What is the primary function of the TRICONEX 3806E?
It is a TMR analog output module that converts safety-controller output commands into field current signals. It provides six 4–20 mA channels and two high-current 20–320 mA channels.
Q2: Which channels provide the 20–320 mA output?
Points 1 and 5 provide the two high-current outputs. The remaining six channels provide 4–20 mA signals. Confirm terminal assignments against the applicable ETP wiring documentation.
Q3: Can the 3806E drive servo valves?
Yes. Its two 20–320 mA outputs are intended for high-current control applications, including suitable servo actuators and turbomachinery control equipment. Verify the actuator’s current demand, load resistance, polarity, and power requirements before connection.
Q4: Is the 3806E a TMR module?
Yes. It receives output information from the three Tricon main processor channels and uses hardware voting to select a healthy channel for output operation.
Q5: What does the LOAD indicator mean?
The LOAD indicator is associated with output-load or loop-condition diagnostics. An abnormal indication may point to an open circuit, missing loop power, wiring fault, or field-load problem. Check the module diagnostics and field circuit before replacing the module.
Q6: Why is an analog output lower than the commanded value?
Possible causes include insufficient loop voltage, excessive load resistance, loose terminals, incorrect wiring, or a field device drawing more current than the circuit can supply. Check the output channel and loop-power conditions independently.
Q7: Can the 3806E replace a 3805E?
Not as a direct plug-and-play replacement. The 3805E provides eight standard 4–20 mA outputs, while the 3806E has six standard outputs and two high-current outputs. Channel allocation, termination hardware, and application configuration must be checked.
Q8: Can the 3806E replace a 3807?
No direct substitution should be assumed. The 3807 provides four bipolar -60 to +60 mA outputs, while the 3806E provides unipolar 4–20 mA and 20–320 mA outputs. Their field-device interfaces and control applications differ.
Safety Precautions
- ⚠️ Treat all connected output circuits as potentially energized, including external loop-power supplies.
- 🔒 Isolate external loop power and follow approved lockout/tagout procedures before disconnecting field wiring.
- ⚡ Verify polarity and voltage before connecting actuators or servo valves.
- 🚫 Never connect a high-current output to a standard 4–20 mA input without confirming electrical compatibility.
- 🧤 Use ESD protection when handling the module and its connectors.
- 📋 Do not modify channel assignments or controller configuration without approved engineering documentation.
- 🛠️ Perform replacement and testing under the site’s safety-system maintenance procedures.
- 🧪 Verify the complete control loop and required safety functions before returning the process to operation.
Recommended TRICONEX Related Models
The following are related Tricon I/O and system modules. They are not all direct replacements for the 3806E.
- TRICONEX 3805E – TMR Analog Output Module
- TRICONEX 3805H – HART Analog Output Module
- TRICONEX 3807 – Bipolar Analog Output Module
- TRICONEX 3703E – Analog Input Module
- TRICONEX 3704E – Analog Input Module
- TRICONEX 3706A – Analog Input Module
- TRICONEX 3708E – Thermocouple Input Module
- TRICONEX 3721 – Analog Input Module
- TRICONEX 3625A – Digital Output Module
- TRICONEX DO3401 – Digital Output Module
- TRICONEX 3503E – Pulse Input Module
- TRICONEX 3511 – Pulse Input Module
- TRICONEX 3008 – Enhanced Main Processor
- TRICONEX 8110 – Main Chassis
- TRICONEX 8311 – High-Density Power Module