The ABB LD 800HSE (3BDH000320R02) is a FOUNDATION Fieldbus Linking Device designed to connect H1 fieldbus networks to a High Speed Ethernet (HSE) subnet. It provides a communication gateway between field instruments and supervisory or control systems, allowing process data and device information to be exchanged across different FOUNDATION Fieldbus network levels.
The module provides one 10/100 Mbps Ethernet HSE interface and four independent FOUNDATION Fieldbus H1 channels. Each H1 channel operates at 31.25 kbit/s and supports Link Master functionality, including Link Active Scheduler (LAS) operation. The four H1 links are galvanically isolated and use pluggable three-pole screw terminals.
The LD 800HSE supports device discovery, access to field-device function blocks, configuration and management through the HSE network, and data republishing between H1 links or between H1 and HSE. It also supports redundant operation when paired with a compatible LD 800HSE and the dedicated redundancy link cable.
This version, 3BDH000320R02, corresponds to hardware version 1.1y. It is intended for safe-area installation; it must not be treated as the hazardous-area-certified LD 800HSE EX version.

LD 800HSE 3BDH000320R02
Product Datasheet
| Parameter | Specification |
|---|---|
| Brand | ABB |
| Model | LD 800HSE |
| Order Number | 3BDH000320R02 |
| Product Type | FOUNDATION Fieldbus Linking Device |
| Product Series | ABB Freelance / Fieldbus Infrastructure |
| Main Function | HSE-to-H1 fieldbus gateway |
| HSE Interface | 1 Ethernet port |
| Ethernet Standard | 10BASE-T / 100BASE-TX |
| Ethernet Speed | 10 or 100 Mbps, auto-sensing |
| H1 Interfaces | 4 independent channels |
| H1 Protocol | FOUNDATION Fieldbus H1 |
| H1 Transmission Rate | 31.25 kbit/s |
| H1 Connectors | 3-pole pluggable screw terminals |
| H1 Isolation | Galvanically isolated, transformer-coupled |
| H1 Link Function | Link Master / Link Active Scheduler |
| Serial Interface | RS-232, 9-pin male Sub-D |
| Serial Speed | Up to 115.2 kbit/s |
| Power Supply | External 24 V DC |
| H1 Bus Power | H1 links require separate power |
| Redundancy | Supported with compatible linking device and redundancy cable |
| Hardware Version | 1.1y |
| Mounting | 35 mm DIN rail |
| Protection Rating | IP20 |
| Operating Temperature | 0 to +55 °C |
| Storage Temperature | -20 to +70 °C |
| Relative Humidity | 0–95%, non-condensing |
| Dimensions | 47 × 131 × 111 mm (L × H × W) |
| Weight | Approximately 0.4 kg |
| Country of Origin | Confirm from product label |
| Product Status | Legacy product; verify current availability |
| Condition | Confirm actual supplied unit |
Technical Features & Specifications
1. HSE-to-H1 Gateway Communication
The LD 800HSE connects FOUNDATION Fieldbus H1 devices to an HSE Ethernet subnet. This architecture allows field instruments operating on lower-speed H1 segments to communicate with supervisory and control-system applications through the Ethernet backbone.
2. Four Independent H1 Channels
The module provides four independent H1 fieldbus links, each operating at 31.25 kbit/s. Each channel supports Link Master functionality and can manage communication scheduling on its own segment.
The H1 interfaces are galvanically isolated and use pluggable three-pole screw terminals for field wiring.
3. HSE Ethernet Interface
One 10/100BASE-TX Ethernet interface provides the connection to the HSE subnet. The interface automatically detects the supported network speed, simplifying connection to compatible Ethernet infrastructure.
4. Field Device Management
The linking device supports identification and access to connected H1 field devices. Through the HSE network, engineering and supervisory systems can access device function blocks and perform supported configuration and management operations.
5. Data Republishing
The LD 800HSE supports data republishing between H1 links and between H1 and HSE. This function allows process information from one fieldbus segment to be made available to other compatible network participants.
6. Redundant Operation
The LD 800HSE supports redundant configurations using two compatible linking devices. A dedicated redundancy link connects the primary and secondary devices and supports redundancy monitoring and failover.
For a redundant pair, follow ABB’s hardware-version restrictions. Do not mix different article numbers within a redundant set during normal plant operation.
7. External Power Requirements
The linking device requires an external 24 V DC supply. The H1 fieldbus segments must be powered separately; the module does not replace the required H1 bus power conditioners.