Description
Product Description
The ABB LD 800HSE, order number 3BDH000320R02, is a FOUNDATION Fieldbus Linking Device designed to connect a High-Speed Ethernet (HSE) subnet with FOUNDATION Fieldbus H1 field-device networks.
The device provides one Ethernet HSE interface and four independent H1 fieldbus links. It acts as a gateway between the supervisory or control system and field instruments, allowing configuration, monitoring, and access to function blocks in connected H1 devices.
Each H1 channel operates as an independent Link Master with Link Active Scheduler (LAS) functionality. The device also supports process-data republishing between H1 links and between H1 and HSE networks.
The LD 800HSE can be used in redundant configurations with a second linking device and a dedicated redundancy connection. This makes it suitable for process automation installations requiring continuous fieldbus communication and centralized device management.
The 3BDH000320R02 version corresponds to hardware version 1.1y. It is designed for safe-area installation. For hazardous-area applications, the dedicated LD 800HSE EX version must be selected.

LD 800HSE 3BDH000320R02
Product Datasheet
| Parameter | Description |
|---|---|
| Brand | ABB |
| Model | LD 800HSE |
| Order Number | 3BDH000320R02 |
| Hardware Version | 1.1y |
| Product Name | FOUNDATION Fieldbus Linking Device |
| Product Type | HSE/H1 Fieldbus Gateway |
| System Application | ABB Freelance / compatible ABB control systems |
| HSE Interface | 1 Ethernet channel |
| Ethernet Standard | 10BASE-T / 100BASE-TX |
| Ethernet Speed | 10 / 100 Mbit/s, auto-sensing |
| H1 Interfaces | 4 independent channels |
| H1 Communication Speed | 31.25 kbit/s |
| H1 Connector | Three-pole pluggable screw terminals |
| Serial Interface | RS-232, 9-pin male Sub-D |
| Serial Speed | Up to 115.2 kbit/s |
| Power Supply | External 24 V DC |
| H1 Segment Power | Supplied separately |
| Mounting | 35 mm DIN rail |
| Protection Rating | IP20 |
| Dimensions | 47 × 131 × 111 mm |
| Approximate Weight | 0.4 kg |
| Operating Temperature | 0 to +55 °C |
| Storage Temperature | -20 to +70 °C |
| Relative Humidity | 0–95%, non-condensing |
Technical Features & Specifications
- HSE-to-H1 gateway: Connects the FOUNDATION Fieldbus HSE Ethernet backbone with up to four H1 fieldbus segments.
- Four independent H1 links: Provides four separate H1 communication channels, each supporting a fieldbus segment operating at 31.25 kbit/s.
- Independent Link Master operation: Each H1 channel can operate as a Link Master with its own Link Active Scheduler.
- Ethernet connectivity: Provides one 10/100 Mbit/s Ethernet interface for communication with the HSE subnet.
- Device management: Supports access to connected H1 devices through system management and network management functions.
- Function block access: Allows supervisory and control applications to access function blocks in connected FOUNDATION Fieldbus instruments.
- Process-data republishing: Supports data exchange between H1 links and between H1 and HSE networks.
- Redundant operation: Supports redundant linking-device arrangements using a dedicated redundancy connection between primary and secondary units.
- External power supply: Requires an external 24 V DC supply. The H1 fieldbus segments must be powered separately.
- Galvanically isolated H1 interfaces: The H1 ports use transformer coupling and galvanic isolation.
- Configuration and firmware: Supports fieldbus configuration and firmware updates through the applicable ABB engineering and device-management tools.
- Compact installation: Uses a 35 mm DIN-rail mounting arrangement with an IP20 enclosure for installation inside a control cabinet.
Application Scenarios
- Distributed control systems: Connects FOUNDATION Fieldbus instruments to compatible ABB supervisory and control platforms.
- Process instrumentation: Integrates field transmitters, positioners, and other compatible H1 devices into the HSE network.
- Power generation: Supports fieldbus communication in power plant process control and auxiliary systems.
- Oil and gas facilities: Provides communication infrastructure for FOUNDATION Fieldbus-based instrumentation networks.
- Chemical and petrochemical plants: Supports centralized instrument configuration, diagnostics, and process-data exchange.
- Redundant control networks: Provides redundant HSE/H1 linking-device arrangements for applications requiring communication availability.
- Legacy system maintenance: Serves as a replacement spare for existing installations using the LD 800HSE hardware version.
First-Time Installation Checklist
- Confirm the complete order number 3BDH000320R02.
- Verify the hardware version. This order number corresponds to hardware version 1.1y.
- Confirm that the host control system and engineering software support the installed LD 800HSE version.
- Install the unit on a suitable 35 mm DIN rail inside an appropriate control cabinet.
- Verify the external 24 V DC power supply and polarity.
- Provide separate power conditioning and power supply arrangements for the H1 segments.
- Connect the HSE Ethernet interface to the correct network segment.
- Connect each H1 fieldbus segment using the correct three-pole terminal assignments.
- Check cable shielding, grounding, bus termination, and segment power arrangements.
- Verify that each H1 segment has an appropriate Link Active Scheduler configuration.
- For redundant operation, verify the dedicated redundancy cable and matching hardware configuration.
- Configure the linking device using the applicable ABB engineering tools.
- Check communication with all connected H1 field devices.
- Verify normal status indications and confirm that device diagnostics are available.
- Record the installed order number, hardware version, firmware, and network configuration.
Daily Maintenance
- Monitor the device status and communication diagnostics through the ABB engineering environment.
- Check HSE Ethernet connectivity and investigate recurring communication interruptions.
- Review H1 segment diagnostics for device communication errors or bus disturbances.
- Inspect the 24 V DC power supply and confirm stable operating voltage.
- Check H1 segment power conditioners and termination arrangements.
- Inspect Ethernet and fieldbus cables for loose connections or physical damage.
- Monitor redundant-device status and investigate failover or synchronization alarms.
- Keep the DIN-rail cabinet clean, dry, and adequately ventilated.
- Maintain records of hardware versions, firmware updates, network settings, and replacement history.
- Avoid modifying fieldbus configuration during an active redundant-device replacement unless permitted by the ABB procedure.
Troubleshooting & Frequently Asked Questions
Q1: What is the main function of the ABB LD 800HSE?
A: It connects a FOUNDATION Fieldbus HSE Ethernet subnet with up to four H1 fieldbus segments, allowing supervisory systems to communicate with field instruments.
Q2: How many H1 channels does it support?
A: The LD 800HSE provides four independent H1 channels, each operating at 31.25 kbit/s.
Q3: Does the module require an external power supply?
A: Yes. The LD 800HSE requires an external 24 V DC supply. The H1 fieldbus links must be powered separately.
Q4: Can the LD 800HSE operate redundantly?
A: Yes. Two linking devices can be configured as a redundant pair using a dedicated redundancy link. The corresponding H1 ports are connected to the same H1 segment.
Q5: What is the difference between 3BDH000320R0101 and 3BDH000320R02?
A: The 3BDH000320R0101 corresponds to hardware version 1.0x, while 3BDH000320R02 corresponds to hardware version 1.1y. ABB documents restrictions on mixing these article numbers in redundant configurations, particularly during online replacement and hardware downgrades.
Q6: Can the standard LD 800HSE be installed in a hazardous area?
A: No. The standard LD 800HSE is intended for safe-area installation. The LD 800HSE EX version, order number 3BSE073314R1, is the designated hazardous-area version for its approved application.
Q7: Does it support EtherNet/IP?
A: Its documented primary function is FOUNDATION Fieldbus HSE-to-H1 linking. It should not be specified as an EtherNet/IP adapter or scanner.
Q8: What should be checked if an H1 field device cannot communicate?
A: Check the H1 segment power, cable polarity, termination, shielding, device address, Link Active Scheduler configuration, and the linking-device diagnostics.
Q9: Can this module directly replace every LD 800HSE version?
A: No. Hardware-version and redundancy restrictions apply. Check the installed article number, hardware version, and ABB replacement instructions before changing the device.
Safety Precautions
- Disconnect the external 24 V DC supply before performing wiring or installation work.
- Follow the plant’s electrical isolation and lockout/tagout procedures.
- Verify that H1 segment power supplies are isolated before working on fieldbus wiring.
- Use appropriate electrostatic discharge protection when handling the electronic device.
- Do not connect or disconnect fieldbus terminals while energized unless the approved procedure permits it.
- Maintain correct polarity, shielding, and grounding according to ABB installation documentation.
- Do not install the standard LD 800HSE in hazardous areas.
- Use only the approved LD 800HSE EX version where hazardous-area certification is required.
- Follow ABB hardware-version restrictions when working with redundant pairs.
- Installation and commissioning should be performed by qualified industrial automation personnel.
Recommended Related Models & Components
The following products are associated with ABB FOUNDATION Fieldbus infrastructure and LD 800HSE installations. They are related accessories or network components, not guaranteed direct replacements.
- ABB 3BDH000320R0101 – LD 800HSE, earlier hardware version
- ABB 3BSE073314R1 – LD 800HSE EX hazardous-area version
- ABB 3BDH000281R1 – LD 800HSE Redundancy Link Cable
- ABB 3KXN617110L0010 – NGP110 H1 Power Conditioner
- ABB 989016x – NFC080-NO FOUNDATION Fieldbus H1 Cable family
- ABB 3BDD011678R0801 – LD 800HSE and LD 800HSE EX documentation media, version 3.6.0
- ABB 3BDD011677R0501 – LD 800HSE User Instructions, version 3.3.0
- ABB 3BDD011677-600 – LD 800HSE Device Management User Instructions
- ABB LD 800HSE – FOUNDATION Fieldbus HSE/H1 Linking Device
- ABB LD 800HSE EX – Hazardous-area FOUNDATION Fieldbus Linking Device
- ABB NGP110 – FOUNDATION Fieldbus H1 Power Conditioner
- ABB FOUNDATION Fieldbus H1 – Fieldbus communication segment components
- ABB FOUNDATION Fieldbus HSE – High-Speed Ethernet network components
- ABB Freelance – Distributed Control System platform
- ABB System 800xA – Distributed control and field-device management platform
Confirm the full article number, hardware version, power supply, fieldbus configuration, and redundancy requirements before selecting related components.