The GE Fanuc IC695CRU320-EJ is a Redundancy CPU for the PACSystems RX3i programmable automation controller platform. Designed for hot-standby (HSB) applications, it operates as part of a dual-CPU control arrangement, where primary and backup controllers synchronize application data to support rapid transfer of control following a CPU or system fault. The module uses a 1 GHz Intel Celeron M processor and provides 64 MB of battery-backed user RAM and 64 MB of non-volatile flash memory. It supports Ladder Diagram, Structured Text, Function Block Diagram, and C programming, with RS-232 and RS-485 serial communication interfaces. Redundancy synchronization is implemented through compatible Memory Xchange modules, such as the IC695RMX128 or IC695RMX228, and the system must be configured using a compatible version of Proficy Machine Edition. The IC695CRU320-EJ is a specific hardware and firmware revision, so replacement planning should account for the installed firmware, partner CPU, redundancy modules, rack configuration, and application backup.

IC695CRU320-EJ
Product Datasheet
| Parameter | Specification |
|---|---|
| Brand | GE Fanuc / GE Intelligent Platforms |
| Model | IC695CRU320-EJ |
| Series | PACSystems RX3i |
| Product Name | Redundancy CPU |
| Product Type | Hot-Standby Redundancy Processor |
| Processor | Intel Celeron M, 1 GHz |
| User Memory | 64 MB battery-backed RAM |
| Flash Memory | 64 MB non-volatile flash |
| Programming Languages | Ladder Diagram, Structured Text, Function Block Diagram, C |
| Serial Interfaces | 1 × RS-232 and 1 × RS-485 |
| Serial Protocols | SNP, Modbus RTU Slave, Serial I/O |
| Redundancy Architecture | Dual-CPU Hot-Standby |
| Redundancy Modules | Compatible IC695RMX128 / IC695RMX228 |
| Maximum Data Transfer | Up to 2 MB |
| Program Blocks | Up to 512; maximum 128 KB per block |
| Discrete Reference Tables | 32 Kbits each for %I and %Q |
| Analog Reference Tables | Up to 32 Kwords each for %AI and %AQ |
| Backplane | RX3i PCI and high-speed serial backplane |
| Power Requirements | +3.3 V DC at 1.0 A; +5 V DC at 1.2 A nominal |
| Switchover Time | Maximum one logic scan; minimum 3.133 ms |
| Operating Temperature | 0 to 60°C |
| Dimensions | Not verified |
| Weight | Not verified for the -EJ revision |
| Country of Origin | Not verified |
| Product Status | Not verified; confirm physical condition with seller |
| Firmware Revision | 7.15 |
| Discontinued | Legacy product; verify current manufacturer support and replacement availability |
First-Time Operation Inspection Checklist
- 🔎 Part number: Confirm the complete IC695CRU320-EJ designation and hardware revision.
- 🧩 Rack compatibility: Verify the RX3i rack, slot arrangement, power supply, and backplane configuration.
- 🔄 Redundancy pairing: Confirm that both CPUs use supported CRU320 configurations and compatible firmware.
- 🔗 Synchronization links: Inspect the IC695RMX128 or IC695RMX228 Memory Xchange modules and associated communication connections.
- 🔋 Battery condition: Check the approved memory-retention battery and verify that the battery status indicator is normal.
- 💻 Program compatibility: Confirm that the project can be opened and maintained with the installed Proficy Machine Edition version.
- 🧪 Failover test: Perform a controlled redundancy switchover test under an approved commissioning procedure.
- 📋 Backup records: Save the application, hardware configuration, firmware information, and redundancy settings before commissioning.
Daily Maintenance
- 🔋 Monitor the battery indicator and replace the memory-retention battery according to the manufacturer’s procedure.
- 🌡️ Keep the control cabinet within the specified 0 to 60°C operating range.
- 🔍 Check CPU status LEDs for CPU OK, RUN, OUTPUTS ENABLED, BATTERY, and SYS FLT indications.
- 🔗 Inspect redundancy communication connections and verify synchronization status.
- 💻 Review controller diagnostics, fault logs, and communication errors.
- 🧹 Maintain cabinet ventilation and remove dust without exposing energized electronics.
- 📝 Record CPU operating status, firmware revision, battery replacement dates, and redundancy test results.
Troubleshooting and Frequently Asked Questions
Q1: What is the main function of the IC695CRU320-EJ?
It executes RX3i control logic and supports hot-standby redundancy. In a properly configured redundant system, a backup CPU can assume control if the active CPU fails.
Q2: Can one IC695CRU320-EJ operate as a complete redundant system by itself?
No. A hot-standby arrangement requires a second compatible redundancy CPU and the appropriate Memory Xchange hardware and synchronization configuration.
Q3: Which redundancy modules are used with this CPU?
The IC695RMX128 and IC695RMX228 are associated Memory Xchange modules. Confirm the hardware and firmware revisions against the system’s redundancy design before installation.
Q4: What does the EJ suffix mean?
The EJ revision is associated with firmware version 7.15. It is important to preserve the exact suffix when identifying the installed unit and checking firmware compatibility.
Q5: Does the CPU have built-in Ethernet?
The CPU provides RS-232 and RS-485 serial interfaces. Ethernet communication is provided through a compatible rack-based Ethernet interface module, such as the IC695ETM001.
Q6: What should be checked if redundancy synchronization fails?
Check CPU firmware compatibility, Memory Xchange module status, synchronization-link connections, hardware configuration, and diagnostic logs. Also verify that both CPUs have matching application and data-transfer configurations.
Q7: Can the IC695CRU320-EJ replace another CRU320 revision directly?
Not automatically. Hardware compatibility, firmware upgrade or downgrade requirements, redundancy partner revision, and Proficy Machine Edition project compatibility must be checked before substitution.
Safety Precautions
- ⚠️ Follow the approved shutdown and isolation procedure before removing or installing the CPU.
- 🔌 Do not insert or remove the module unless the rack and system documentation explicitly permits the operation.
- 🧤 Use ESD protection when handling the CPU and its backplane connector.
- 🔋 Use only manufacturer-approved battery types and observe battery polarity.
- 🔄 Do not test redundancy failover on a live process without an approved operating procedure and process safeguards.
- 💾 Back up the application and configuration before firmware changes or CPU replacement.
- 📘 Follow GE Fanuc / Emerson PACSystems RX3i documentation for installation, configuration, and commissioning.
Recommended GE Fanuc Related Models
The following models are related to the PACSystems RX3i platform, redundancy architecture, and controller expansion. They are not all direct replacements for IC695CRU320-EJ.
- GE IC695CRU320
- GE IC695RMX128
- GE IC695RMX228
- GE IC695CMX128
- GE IC695ETM001
- GE IC695ETM002
- GE IC695PSD040
- GE IC695PSA040
- GE IC695PSD140
- GE IC695PSA140
- GE IC695CHS012
- GE IC695CHS016
- GE IC695CPE305
- GE IC695CPE310
- GE IC695CPE330