Description
Product Description
The ABB PM861AK01 (3BSE018157R1) is a processor unit for the ABB AC 800M distributed control system, designed for industrial process automation and integration with System 800xA. It executes control applications, manages communication with distributed I/O stations, and coordinates data exchange with fieldbus and supervisory systems. Based on a 48 MHz MPC860 processor, the unit provides 16 MB of memory and supports CPU redundancy when configured with a compatible partner processor and RCU-Link infrastructure. Its TP830 baseplate provides two Ethernet control-network ports and two serial interfaces, including an RS-232C port and an isolated configuration-tool interface. The PM861AK01 kit includes the PM861A CPU, TP830 baseplate, CEX-Bus and ModuleBus terminators, RCU-Link terminator, memory backup battery, and power connector. It is configured using ABB Control Builder within a compatible engineering environment. Before replacement, verify controller firmware, application compatibility, CEX-Bus modules, ModuleBus topology, and redundancy configuration.

PM861AK01 3BSE018157R1
Product Datasheet
| Parameter | Specification |
|---|---|
| Brand | ABB |
| Model | PM861AK01 |
| Part Number | 3BSE018157R1 |
| Series | AC 800M / System 800xA |
| Product Name | Processor Unit |
| Product Type | Central Processing Unit (CPU) |
| Processor | MPC860, 32-bit RISC |
| Clock Frequency | 48 MHz |
| Total Memory | 16 MB |
| Application Memory | Approximately 7.155 MB |
| Flash Memory | Available for firmware and application storage |
| Control Performance | 0.23 ms per 1,000 Boolean operations |
| Ethernet Interfaces | 2 × RJ45 control-network ports, 10 Mbps |
| Serial Interfaces | 2 × RJ45: COM3 RS-232C and isolated COM4 configuration interface |
| Communication Buses | CEX-Bus, ModuleBus, RCU-Link |
| CEX-Bus Capacity | Up to 12 communication modules |
| I/O Capacity | Up to 96 S800 I/O modules in non-redundant configurations; system-dependent |
| CPU Redundancy | Supported with compatible redundant processor configuration |
| Power Supply | 24 V DC nominal |
| Supply Voltage Range | 19.2–30 V DC |
| Power Consumption | 6.0 W typical; 10.3 W maximum |
| Operating Temperature | 0 to +60°C |
| Storage Temperature | -40 to +70°C |
| Relative Humidity | 5–95%, non-condensing |
| Protection Rating | IP20 |
| Mounting | DIN rail using TP830 baseplate |
| Dimensions | 135 × 186 × 119 mm (depth × height × width) |
| Net Weight | Approximately 1.2 kg |
| Country of Origin | China listed in product records; verify individual unit |
| Kit Contents | PM861A CPU, TP830, TB850, TB807, TB852, backup battery, and 4-position power plug |
| Product Status | Classic lifecycle status |
| Discontinued | Legacy product; check ABB availability and replacement guidance |
First-Time Operation Inspection Checklist
- 🔎 Part-number verification: Confirm PM861AK01 and 3BSE018157R1 on the nameplate.
- 🧩 Kit inspection: Check the CPU, TP830 baseplate, terminators, power connector, and memory backup battery.
- ⚡ Power supply: Verify 24 V DC supply and ensure the voltage remains within 19.2–30 V DC.
- 🌐 Ethernet connection: Check CN1 and CN2 network connections and verify the correct control-network topology.
- 🔌 Serial interfaces: Confirm COM3 and COM4 assignments before connecting engineering equipment.
- 🔄 Redundancy configuration: If used in a redundant system, verify partner CPU compatibility and RCU-Link connections.
- 🧱 Bus termination: Confirm TB850, TB807, and TB852 are installed at their correct bus positions.
- 💻 Software compatibility: Check Control Builder version, controller firmware, application backup, and hardware configuration.
- 🧪 Functional testing: Verify CPU startup, controller diagnostics, I/O communication, and application execution.
- 📋 Backup: Save the application, hardware configuration, firmware information, and controller parameters before commissioning.
Daily Maintenance
- 🔍 Inspect the CPU, baseplate, and DIN-rail mounting for mechanical damage.
- 💡 Monitor CPU status LEDs and investigate fault or diagnostic indications.
- ⚡ Check the 24 V DC supply for fluctuations and abnormal power conditions.
- 🌐 Monitor Ethernet communication and investigate repeated network interruptions.
- 🔄 Review RCU-Link and CEX-Bus diagnostics where redundancy or communication modules are installed.
- 🔋 Monitor the memory backup battery condition and replace it according to ABB procedures.
- 🌡️ Maintain cabinet temperature and ventilation within the specified limits.
- 🧹 Keep the IP20 assembly free from conductive dust, moisture, and contamination.
- 📝 Record controller alarms, firmware changes, battery replacement, and maintenance activities.
Troubleshooting and Frequently Asked Questions
Q1: What is the main function of the PM861AK01?
It executes AC 800M control applications and manages communication with distributed I/O, communication interfaces, and supervisory systems.
Q2: Does the PM861AK01 support CPU redundancy?
Yes. The PM861A processor supports redundant CPU configurations when paired with a compatible processor and the required RCU-Link hardware. The PM861AK01 itself is a single-processor kit; the redundant kit is PM861AK02.
Q3: What is included in the PM861AK01 package?
The standard kit includes the PM861A CPU, TP830 baseplate, TB850 CEX-Bus terminator, TB807 ModuleBus terminator, TB852 RCU-Link terminator, memory backup battery, and four-position power plug.
Q4: What is the difference between PM861AK01 and PM861AK02?
PM861AK01 is a single processor unit kit. PM861AK02 is a redundant processor unit kit containing two PM861AK01 units, a TK850 CEX-Bus expansion cable, and a TK851 RCU-Link cable.
Q5: Which engineering software is used?
ABB Control Builder is used to configure and maintain AC 800M controllers within a compatible System 800xA engineering environment. Confirm software and firmware compatibility before modifying an existing project.
Q6: Can the PM861AK01 replace PM864AK01?
Not as an assumed direct replacement. The PM864A has different processing performance and memory characteristics. Check application resource requirements, firmware, hardware configuration, and ABB migration documentation before substitution.
Q7: What should be checked if the controller fails to communicate with S800 I/O?
Check ModuleBus termination, baseplate connections, I/O module status, controller diagnostics, and the hardware configuration. For communication interfaces, also inspect CEX-Bus connections and the associated module configuration.
Q8: What happens if the memory backup battery fails?
A failed or depleted battery can affect memory retention during power loss. Check the battery status and follow ABB’s replacement procedure. Back up the application and controller configuration before battery maintenance.
Safety Precautions
- ⚠️ Follow the approved shutdown and isolation procedure before removing the processor.
- ⚡ Verify the 24 V DC supply polarity and voltage before connecting power.
- 🧤 Use ESD protection when handling the CPU and baseplate connectors.
- 🔒 Do not disconnect CEX-Bus, ModuleBus, or RCU-Link connections while the system is operating unless the approved procedure permits it.
- 🔋 Replace the memory backup battery using the specified ABB procedure.
- 💾 Back up the controller application and configuration before firmware changes or hardware replacement.
- 🌐 Confirm network connections and controller redundancy status before returning the process to automatic operation.
- 📘 Follow ABB AC 800M controller hardware and System 800xA engineering documentation.
Recommended ABB Related Models
The following products are related to the AC 800M processor and communication architecture. They are not all direct replacements for PM861AK01.
- ABB PM861A – 3BSE018105R1
- ABB PM861AK02 – 3BSE018160R1
- ABB PM864AK01 – 3BSE018161R1
- ABB PM864AK02 – 3BSE018164R1
- ABB PM865K01 – 3BSE031151R1
- ABB PM866K01 – 3BSE050198R1
- ABB PM867K01 – 3BSE076355R1
- ABB PM856K01 – 3BSE018104R1
- ABB PM851K01 – 3BSE018168R1
- ABB CI854AK01 – 3BSE030220R1
- ABB CI840 – 3BSE022457R1
- ABB CI867K01 – 3BSE043660R1
- ABB BC810K01 – 3BSE031154R1
- ABB TP830 – 3BSE018114R1
- ABB TU846 – 3BSE022460R1