Description
Product Description
The DEIF SCM-1 is a multifunctional synchronizing, generator breaker control, and electrical measurement module designed for the DEIF Delomatic generator control system. Installed as a plug-in module in a Delomatic Generator Unit (DGU) rack, it manages synchronization and electrical supervision for one generator set. The module measures three-phase generator and busbar electrical values, evaluates voltage, frequency, and phase-angle differences, and controls breaker closing and opening according to configured synchronization conditions. Its control functions also support generator speed and voltage regulation through compatible electronic governor and automatic voltage regulator interfaces. Optional OPR-1 relay boards can provide relay outputs for mechanical speed governors or voltage regulators. The SCM-1 is intended for marine power management, auxiliary generator systems, and industrial generator installations where accurate synchronization and coordinated breaker control are required. Before replacement, verify the exact SCM-1 hardware revision, rack configuration, I/O address, voltage-measurement jumpers, CT/VT ratios, and installed output boards against the existing system documentation.

DEIF SCM-1
Product Datasheet
| Parameter | Specification |
|---|---|
| Brand | DEIF |
| Model | SCM-1 |
| Part Number Reference | 2034220009; verify against the module label |
| Series | DEIF Delomatic |
| Product Name | Synchronizing and Measuring Module |
| Product Type | Generator control and measurement module |
| Primary Application | Generator synchronization, breaker control, and electrical measurement |
| System Installation | Plug-in module for a compatible Delomatic DGU rack |
| Generator Capacity | Controls one generator set per SCM-1 |
| Voltage Measurement | Three-phase generator voltage and three-phase busbar voltage |
| Current Measurement | Three-phase CT inputs; -/1 A or -/5 A configurations |
| Voltage Input Range | Configurable ranges up to 690 V AC phase-to-phase; confirm jumper configuration |
| Frequency Measurement | 40–70 Hz measurement range |
| Synchronizing Frequency Range | 45–65 Hz |
| Synchronizing Method | Dynamic synchronization using frequency, voltage, and phase-angle differences |
| Synchronizing Control | Programmable synchronization conditions and breaker closing-time compensation |
| Measurement Functions | Voltage, current, frequency, active power, reactive power, apparent power, and power factor |
| Governor Interface | Analog control for compatible electronic speed governors |
| AVR Interface | Analog control for compatible electronic voltage regulators |
| Mechanical Control Option | Optional OPR-1 relay boards |
| Breaker Control | Generator circuit-breaker ON/OFF control |
| Breaker Feedback | Binary feedback inputs for breaker status |
| Supply Voltage | 24 V DC nominal through the Delomatic system; verify rack supply arrangement |
| Power Consumption | Approx. 2 W typical from backplane and additional supply requirements; verify the applicable hardware documentation |
| I/O Address Configuration | DIP switch S2 on the SCM-B board |
| Voltage Range Configuration | Jumpers on the SCM-C board |
| Protection Class | IP20 when installed in the designated rack |
| Operating Temperature | Exact rating depends on the applicable hardware documentation and installation conditions |
| Dimensions | Approx. 91.4 mm module width; full dimensions not verified |
| Weight | Not verified; supplier listings report different values |
| Country of Origin | Denmark (DEIF manufacturer); individual unit origin not verified |
| Product Status | Legacy / discontinued reference; confirm availability and revision |
| Discontinued | Reported discontinued by industrial spare-parts distributors; confirm current status with DEIF |
First-Time Operation Inspection Checklist
- 🔍 Model verification: Confirm the SCM-1 designation, part number, hardware revision, and board identification before installation.
- 🔌 Power inspection: Verify the Delomatic rack power supply and connector condition. Do not apply an assumed external supply directly to the module.
- ⚙️ Rack compatibility: Confirm that the DGU rack and associated Delomatic modules support the installed SCM-1 configuration.
- 🧩 I/O address: Record and compare the SCM-B board S2 DIP-switch address with the original configuration.
- 📐 Voltage configuration: Check the SCM-C board jumpers for generator and busbar voltage measurement ranges.
- 🔧 CT/VT verification: Confirm current-transformer ratios, secondary ratings, voltage-transformer ratios, and phase connections.
- 🔄 Control-interface check: Verify the governor and AVR signal types, scaling, polarity, and connected output hardware.
- 🛡️ Breaker circuit inspection: Check breaker close/open wiring, auxiliary contacts, interlocks, and trip circuits.
- 🧪 Functional test: Perform synchronization and breaker-control tests under an approved commissioning procedure before connecting the generator to a live busbar.
Daily Maintenance
- 📊 Review generator voltage, current, frequency, active power, reactive power, and power factor readings.
- 🔍 Check the DGU panel for SCM-1 alarms, abnormal status indications, or communication faults.
- 🔌 Inspect rack connectors and accessible wiring for looseness, corrosion, discoloration, or overheating.
- ⚡ Monitor synchronization behavior and investigate repeated failure to meet voltage, frequency, or phase-angle limits.
- 🧰 Keep the module and its rack environment clean, dry, and within the approved operating conditions.
- 📝 Record parameter changes, protection events, breaker operations, and maintenance activities.
- 🔄 Periodically verify governor, AVR, and breaker feedback signals as part of the generator maintenance schedule.
Troubleshooting and Frequently Asked Questions
Q1: What is the main function of the DEIF SCM-1?
The SCM-1 combines generator synchronization, breaker control, and three-phase electrical measurement. It helps align generator voltage, frequency, and phase angle with the busbar before breaker closing.
Q2: Which DEIF system is the SCM-1 designed for?
It is associated with the DEIF Delomatic generator control system and is installed in a compatible DGU rack. Confirm the rack type and system revision before ordering a replacement.
Q3: Can the SCM-1 control an electronic governor and AVR?
Yes. The module supports analog control interfaces for compatible electronic speed governors and electronic voltage regulators. Signal ranges and wiring must match the original configuration.
Q4: Can it operate with mechanical governors or voltage regulators?
Optional OPR-1 relay boards can be installed for mechanical speed-governor and voltage-regulator control. Confirm the presence and configuration of these boards before commissioning.
Q5: Why does the generator fail to synchronize?
Possible causes include incorrect CT/VT wiring, incorrect voltage-range jumpers, phase-sequence errors, unsuitable synchronization settings, governor or AVR signal problems, or incorrect breaker closing-time compensation. Check the configuration and measurement circuits before changing synchronization settings.
Q6: Why are generator or busbar measurements incorrect?
Check the phase connections, CT and VT ratios, secondary wiring, measurement-range jumpers, and the condition of the sensing circuits. Incorrect scaling or wiring can cause misleading electrical readings.
Q7: Is the SCM-1 interchangeable with the SCM-2?
No automatic interchangeability should be assumed. The SCM-1 is intended for generator synchronization and control, while the SCM-2 is designed for different applications such as shaft-generator or bus-tie control. Confirm the system application and configuration before substitution.
Q8: What should be checked when replacing an SCM-1?
Record the existing I/O address, SCM-C voltage-range jumpers, CT/VT settings, OPR-1 board arrangement, governor and AVR wiring, and breaker feedback configuration. Compare these details with the replacement module before energizing the system.
Safety Precautions
- ⚠️ Isolate the generator, busbar measurement circuits, and relevant control supplies before removing or installing the module.
- ⚡ Treat CT secondary circuits as hazardous. Never open an energized CT secondary circuit; follow the approved shorting procedure.
- 🔒 Apply lockout/tagout procedures and verify the absence of hazardous voltage before handling wiring.
- 🧤 Use appropriate electrical PPE and ESD protection when handling circuit boards.
- 🚫 Never test breaker-closing logic on a live busbar without an approved commissioning plan and all required interlocks.
- 📋 Do not change synchronization limits, protection settings, DIP switches, or voltage-range jumpers without reviewing the system drawings and configuration records.
- 🛠️ Use qualified generator-control personnel for installation, calibration, and functional testing.
Recommended DEIF Related Models
The following are related Delomatic system modules and DEIF generator-control references. They are not all direct replacements for the SCM-1.
- DEIF PSM-1 – Power Supply Module
- DEIF CM-2 – Control Module
- DEIF IPM-1 – Input Module
- DEIF OPM-1 – Output Module
- DEIF SCM-2 – Synchronizing and Control Module
- DEIF CRM-1 – Current Relay Module
- DEIF AOM-1 – Analog Output Module
- DEIF OPR-1 – Optional Relay Board
- DEIF DGU – Generator Unit
- DEIF Delomatic-3 – Generator Control System
- DEIF PCM4 – Power Management Controller
- DEIF PPU-3 – Protection and Power Management Unit
- DEIF AGC-4 – Automatic Generator Controller
- DEIF AGC-4 Mk II – Automatic Generator Controller
- DEIF ASC-4 – Automatic Sustainable Controller