Description
Product Description
The Kongsberg RMP201-8, product number 324400, is an eight-channel Remote Multi-Purpose Input/Output module designed for distributed automation and control systems. It provides configurable analog and digital signal interfacing between field devices and a central control system through Kongsberg’s RBUS communication network.
The module supports voltage and current measurement, analog signal output, and digital output functions. Its eight channels provide flexibility for connecting sensors, transmitters, control signals, and field actuators. Channels 1–5 and 7 include digital output functionality, while channels 6 and 8 have separate galvanic-isolation characteristics.
The RMP201-8 communicates through a redundant A/B RBUS arrangement using an RS-485 physical layer. It is designed for DIN-rail installation and is suitable for distributed I/O applications in marine automation, engine-room monitoring, and vessel control systems.
With a nominal 24 V DC supply and a compact housing, the RMP201-8 is a practical spare-part option for maintaining compatible Kongsberg remote I/O installations.

RMP201-8 324400
Key Technical Specifications
- Brand: Kongsberg Maritime
- Model: RMP201-8
- Product Number: 324400
- Product Type: Remote Multi-Purpose Input/Output Module
- Number of Channels: 8
- Channel Functions: Configurable analog and digital I/O functions
- Analog Input: Voltage, ±10 V; current, 0–20 mA
- Analog Input Resolution: 16-bit ADC
- Analog Input Accuracy: ±0.15% FS
- Analog Output: Voltage, ±10 V; current, 0–20 mA
- Analog Output Resolution: 16-bit DAC
- Voltage Output Load: Maximum 0.1 mA
- Current Output Load: Maximum 500 Ω
- Digital Output: Channels 1–5 and 7
- Digital Output Type: High-side driver
- Digital Output Current: 100 mA per channel
- Digital Output Short-Circuit Protection: 150 mA for 20 ms
- Power Supply: +24 V DC nominal
- Supply Voltage Range: +18 to +32 V DC
- Standby Current: 0.25 A
- Typical Power-On Surge: 1.2 A for 20 ms at 24 V DC
- RBUS Communication: Redundant A/B bus
- Communication Physical Layer: RS-485 multidrop
- RBUS Bit Rate: 2 Mbps
- Signal Encoding: Manchester
- RBUS Connector: 5-pole Phoenix T-BUS connector
- Copper Cable Distance: Maximum 200 m between repeaters, with up to 3 repeaters
- Fiber-Optic Distance: Up to 1,000 m point-to-point with an additional fiber media converter
- Mounting: Snap-on dual DIN rail
- Dimensions: 35 × 130 × 130 mm (W × H × D)
- Weight: Approximately 0.35 kg
- Operating Temperature: -15 to +70°C
- Storage Temperature: -25 to +70°C
- Protection Class: IP20
- Standards: IEC 60945 and IACS E10
Key Features
- Eight configurable channels for flexible field signal integration.
- Supports analog voltage and current input and output.
- 16-bit ADC and DAC conversion for analog signal processing.
- Digital high-side outputs on channels 1–5 and 7.
- Redundant RBUS A/B communication architecture.
- RS-485 multidrop physical layer with 2 Mbps communication.
- Galvanic isolation between the power input and module logic.
- Separate isolation characteristics for channels 6 and 8.
- Configurable I/O soft fail-safe timeout.
- Compact DIN-rail housing for distributed control cabinets.
Application Scenarios and Pain Points
Marine Engine-Room Automation: Collects equipment status and analog measurements from field instruments and transfers signals to the vessel’s automation system.
Shipboard Machinery Monitoring: Supports monitoring of pumps, compressors, cooling systems, and auxiliary machinery through configured field I/O channels.
Remote Equipment Control: Provides analog and digital signal interfaces for remote monitoring and control of field devices.
Marine Power Management: Can be integrated into suitable automation arrangements for generator-related measurements, equipment status, and control signals.
Distributed I/O Expansion: Allows field signal connections to be located closer to equipment, helping reduce long cable runs to centralized control cabinets.
Legacy Kongsberg System Maintenance: Provides a replacement option for installations using the RMP201-8 remote I/O architecture, subject to hardware and software compatibility checks.
Installation and Commissioning
- Confirm the product number 324400 and the RMP201-8 model designation.
- Check the installed RBUS architecture and confirm the required A/B bus connections.
- Verify the 24 V DC supply and ensure that the available voltage remains within the specified operating range.
- Mount the module on a compatible dual DIN-rail arrangement.
- Connect field wiring to the screw-clamp terminals according to the approved wiring diagram.
- Configure each channel for its intended analog or digital function.
- Verify voltage and current signal ranges before connecting field instruments.
- Check the RBUS communication connections, cable length, and repeater arrangement.
- Confirm module communication and field signal values at the host control system.
- Test analog outputs and digital output functions using approved commissioning procedures.
- Verify fail-safe behavior and alarm handling before returning connected equipment to service.
Daily Maintenance
- Inspect the module housing and DIN-rail mounting for mechanical damage.
- Check the 24 V DC supply for abnormal fluctuations.
- Inspect field terminals for looseness, corrosion, or damaged insulation.
- Monitor RBUS communication status and investigate recurring communication faults.
- Compare analog input readings with calibrated reference instruments when required.
- Test digital output channels during scheduled maintenance.
- Inspect A/B bus wiring and cable shielding.
- Maintain updated records of channel assignments and configuration parameters.
Troubleshooting and FAQ
Q1: What is the main function of the RMP201-8?
It is an eight-channel remote multi-purpose I/O module used to interface analog and digital field signals with a compatible Kongsberg automation system.
Q2: What power supply does the RMP201-8 require?
It uses a nominal 24 V DC supply with an operating range of +18 to +32 V DC.
Q3: Does the module support analog signals?
Yes. The documented analog input ranges include ±10 V and 0–20 mA. Analog outputs also support ±10 V and 0–20 mA.
Q4: How many digital output channels are available?
The manufacturer documentation identifies digital outputs on channels 1–5 and 7. Each is specified as a 100 mA high-side driver.
Q5: What communication interface does the RMP201-8 use?
It uses the Kongsberg RBUS network with an RS-485 multidrop physical layer, Manchester encoding, and a 2 Mbps bit rate.
Q6: Can the module operate with redundant communication?
The module provides A/B RBUS connections for the redundant bus arrangement. The actual redundancy behavior depends on the complete network architecture and connected system components.
Q7: What should be checked if communication is interrupted?
Inspect the A/B bus connections, cable condition, termination and repeater arrangement, module power supply, and host-system diagnostics. Verify the network configuration before replacing hardware.
Q8: Can the RMP201-8 be replaced by an RMP420 or RMP422i?
Do not assume direct interchangeability. These are related Kongsberg remote I/O products, but their hardware, channel configuration, and system integration requirements differ. Confirm the applicable system documentation before substitution.
Safety Precautions
- Installation and servicing must be performed by qualified automation or marine electrical personnel.
- Isolate the module and associated field circuits before wiring or removal.
- Verify supply polarity and voltage before energizing the module.
- Follow the manufacturer’s terminal assignments and field-wiring diagrams.
- Do not exceed the specified analog output load or digital output current.
- Maintain the required cable topology and maximum RBUS segment distances.
- Observe the specified isolation limits between channels and the bus.
- Do not bypass fail-safe functions or modify control logic without engineering approval.
- Confirm that the complete installation meets applicable marine electrical and environmental requirements.
Recommended Related Models and Components
The following are related Kongsberg products and system components. They are not all direct replacements for the RMP201-8.
- RMP420 – Remote Multi-Purpose I/O Module
- RMP422i – Remote Multi-Purpose I/O Module
- RDIOR420 – Remote Digital I/O Relay Module
- RDIO420 – Remote Digital Input/Output Module
- RCU502i – Remote Control Unit
- RCU602 – Remote Control Unit
- RHUB200-5 – Communication Hub
- RSER200-4 – Serial Line Interface Module
- MRU-M-MB3 – Motion Reference Unit
- MRU-M-SU1 – Motion Reference Unit Component
- QUINTPS/1AC/24DC/10 – 24 V DC Power Supply
- AutoChief – Kongsberg Marine Engine Control System
- K-Chief 600 – Kongsberg Marine Automation System
- K-Pos – Kongsberg Dynamic Positioning System
Confirm product revisions, network architecture, and host-system compatibility before ordering related components.
Inspection and Quality Control
Before installation, verify the model designation and product number 324400. Inspect the housing, terminal blocks, RBUS connectors, and mounting clips for physical damage or corrosion.
Functional testing should use a compatible Kongsberg RBUS environment. Check the 24 V DC power input, communication over the A/B bus, analog input measurement, analog output response, and digital output operation. Confirm the channel configuration and fail-safe behavior against the approved system documentation.
Record the module identification, hardware revision, test results, and inspection status for maintenance traceability.