Description
Product Description
The Triconex 3623T is a 16-point Supervised Digital Output (SDO) module designed for Tricon safety instrumented systems. Operating with a nominal field voltage of 120 V DC, it provides supervised digital outputs for critical industrial control and shutdown applications.
The module receives output commands from the three Tricon main processor channels. Its fault-tolerant output switching architecture uses voted control signals to operate field loads while monitoring the condition of the output circuits.
The 3623T provides diagnostics for field power, load presence, and fuse conditions. These supervision functions help maintenance personnel identify problems such as loss of field power, open circuits, missing loads, and output wiring faults.
A key specification is its minimum 2,500 V DC point isolation. This distinguishes the 3623T from the standard 3623, which has a specified minimum point isolation of 1,500 V DC.
The module is intended for compatible Tricon v9–v10 system configurations and requires the appropriate external termination panel (ETP) and field wiring arrangement. Verify the installed system revision, termination hardware, and application requirements before replacement.

3623T
Product Datasheet
| Parameter | Description |
|---|---|
| Brand | Triconex |
| Model | 3623T |
| Product Name | Supervised Digital Output Module |
| Module Type | TMR Supervised Digital Output (SDO) |
| System | Tricon Safety Instrumented System |
| System Compatibility | Tricon v9–v10; verify configuration |
| Nominal Field Voltage | 120 V DC |
| Recommended Voltage Range | 90–150 V DC |
| Maximum Voltage | 160 V DC |
| Output Channels | 16, commoned |
| Maximum Current | 0.8 A per point |
| Surge Current | 4 A for 10 ms |
| Minimum Required Load | 30 mA |
| Maximum Load Leakage | 4 mA |
| Point Isolation | 2,500 V DC minimum |
| Logic Power Consumption | Less than 10 W |
| Field Termination Fuse | 1 A fast-acting fuse per output |
| Module Status Indicators | PASS, FAULT, ACTIVE |
| Field Alarm Indicators | POWER, LOAD/FUSE |
| Color Code | Steel Blue |
Technical Features & Specifications
- TMR architecture: Receives output commands from the three main processor channels and uses a fault-tolerant output switching arrangement to provide voted field control signals.
- Supervised digital outputs: Provides 16 commoned output points for compatible 120 V DC field loads.
- High point isolation: Provides a minimum point isolation rating of 2,500 V DC, distinguishing the 3623T from the standard 3623.
- Field circuit monitoring: Voltage and current loopback diagnostics monitor the field circuit and help identify abnormal load conditions.
- Power monitoring: Detects loss of field power and reports associated diagnostic conditions.
- Load supervision: Helps identify missing loads, open field circuits, and load-related faults.
- Fuse monitoring: Works with the field termination fuse arrangement to indicate fuse or load-related problems.
- Output current capacity: Supports up to 0.8 A per output point, with a 4 A surge rating for 10 ms.
- Diagnostic indicators: Provides individual ON/OFF output indications and module-level PASS, FAULT, and ACTIVE status indicators.
- Hot-spare support: Tricon SDO modules support hot-spare configurations when the system hardware and application are configured accordingly.
- External termination: Requires a compatible external termination panel and cable interface to the Tricon backplane.
- Wiring considerations: Triconex recommends compatibility testing for applications with field wiring longer than 100 meters, non-twisted-pair cables, or atypical loads such as smart devices, strobe lights, and klaxons.
Application Scenarios
- Emergency shutdown systems: Controls compatible field devices used in industrial shutdown sequences.
- Process safety systems: Provides supervised digital outputs for safety-related control functions.
- Power generation: Supports output control in compatible turbine and power plant safety systems.
- Oil and gas facilities: Interfaces with suitable 120 V DC field loads in process protection installations.
- Chemical and petrochemical plants: Supports safety-system output circuits requiring field-load supervision.
- Industrial machinery protection: Controls compatible shutdown and protective devices.
- Maintenance and retrofit projects: Provides a matching spare for existing Tricon installations using the 3623T module.
First-Time Installation Checklist
- Verify the complete model number 3623T and compare it with the installed module.
- Confirm that the Tricon system revision and chassis configuration support this module.
- Verify the nominal 120 V DC field supply and ensure the actual voltage remains within the specified operating range.
- Confirm that the installed external termination panel (ETP) and interconnection cable are compatible.
- Check all 16 output assignments against the approved system wiring drawings.
- Verify that each field load meets the minimum required load of 30 mA.
- Check the field termination fuses and confirm the specified 1 A fast-acting fuse arrangement.
- Inspect connectors, terminal wiring, and the module for physical damage or contamination.
- Confirm that field wiring length, cable type, and load characteristics meet application requirements.
- Follow the approved Tricon installation and hot-spare replacement procedures.
- Verify PASS, FAULT, and ACTIVE indicators after installation.
- Test output operation and field-circuit supervision before returning the system to service.
Daily Maintenance
- Monitor module PASS, FAULT, and ACTIVE status indicators.
- Review POWER and LOAD/FUSE alarms for abnormal field conditions.
- Check the output status indicators against the expected process state.
- Investigate recurring field power loss or load supervision alarms.
- Inspect external termination panels and associated cables during scheduled maintenance.
- Verify field supply voltage and load conditions when abnormal output behavior occurs.
- Keep the control cabinet clean, dry, and within the equipment’s specified environmental limits.
- Record module replacement, diagnostic events, and maintenance activities.
- Do not bypass field supervision or alter output wiring without approved engineering authorization.
Troubleshooting & Frequently Asked Questions
Q1: What is the main function of the Triconex 3623T?
A: It provides 16 supervised digital output points for compatible 120 V DC field loads in Tricon safety instrumented systems.
Q2: Is the 3623T a 24 V DC output module?
A: No. The 3623T is a nominal 120 V DC module with a recommended operating range of 90–150 V DC. The Tricon 3624 is a separate 24 V DC supervised output module.
Q3: What is the difference between 3623 and 3623T?
A: Both are 16-point, 120 V DC TMR supervised digital output modules. The specified minimum point isolation is 1,500 V DC for the 3623 and 2,500 V DC for the 3623T.
Q4: How many output channels are available?
A: The module provides 16 commoned output signals.
Q5: What field faults can the module help detect?
A: Its supervision functions help identify loss of field power, blown fuses, missing or open loads, and abnormal field circuit conditions.
Q6: Does the 3623T require an external termination panel?
A: Yes. Tricon SDO modules require a compatible external termination panel and cable interface to the Tricon backplane.
Q7: Can the 3623T support a hot-spare configuration?
A: Tricon SDO modules support hot-spare operation when the system configuration and installation procedure permit it. Confirm the actual chassis and application arrangement.
Q8: What should be checked if a LOAD/FUSE alarm appears?
A: Check the field load, wiring continuity, termination connections, and associated fuse. Follow the system troubleshooting procedure before replacing the module.
Q9: Can the 3623T drive smart devices or long field cables?
A: These applications require additional compatibility testing. Triconex specifically recommends testing for field wiring over 100 meters, non-twisted-pair cable, and atypical loads such as smart devices, strobe lights, or klaxons.
Safety Precautions
- The module operates with nominal 120 V DC field circuits. Isolate the relevant field power before working on external wiring.
- Follow the plant’s lockout/tagout procedures and verify the absence of hazardous voltage.
- Do not remove or insert modules unless the approved Tricon maintenance procedure permits the operation.
- Use appropriate electrostatic discharge protection when handling electronic modules.
- Never bypass safety-system diagnostics or output supervision without formal authorization.
- Verify field wiring polarity, fuse ratings, and load compatibility before energizing the circuit.
- Do not exceed the specified voltage or current ratings.
- Perform functional testing in accordance with the approved safety instrumented system maintenance procedure.
- Only qualified safety-system personnel should perform installation, testing, or troubleshooting.
Recommended Related Models & Components
The following Triconex modules and system components are related to digital output, digital input, and Tricon safety-system applications. They are not all direct replacements for the 3623T.
- Triconex 3623 – 16-point, 120 V DC supervised digital output module
- Triconex 3624 – 16-point, 24 V DC supervised digital output module
- Triconex 3625 – 32-point, 24 V DC supervised/non-supervised digital output module
- Triconex 3611E – Digital output module
- Triconex 3604E – Digital output module
- Triconex 3603B – Digital output module
- Triconex 3503E – Digital input module
- Triconex 3504E – Digital input module
- Triconex 3502E – Digital input module
- Triconex 3511 – Digital input module
- Triconex 3721 – Analog input module
- Triconex 3700A – Analog input module
- Triconex 3805E – Analog output module
- Triconex 8312 – Main processor module
- Triconex 8310 – Power supply module
Confirm the complete model number, system generation, termination panel, and electrical requirements before selecting any related component for a replacement project.