Technical Parameters
- Part Number: 163179-01 (Main PWA) / 163179-01G (Conformal Coated)
- Manufacturer: Bently Nevada (Baker Hughes)
- Monitor Type: 6-Channel Temperature Monitor
- Input Types: Resistance Temperature Detectors (RTDs) & Thermocouples (TC)
- RTD Support: 100 Ω Platinum (385 & 392), 10 Ω Copper, 120 Ω Nickel
- TC Support: Type E, J, K, T
- Resolution: 1°C or 1°F
- Isolation: 500 Vdc (Channel-to-Channel and Channel-to-Backplane)
Product Description
The Bently Nevada 3500/60 is a high-density temperature monitor designed to provide six channels of continuous temperature monitoring within a 3500 Machinery Protection System rack. The module accepts inputs from both RTDs and Thermocouples, processing these signals to compare them against user-programmable alarm setpoints. The 163179-01G version features a “G” suffix, indicating a conformal coating for enhanced protection against moisture, dust, and corrosive contaminants, ensuring long-term reliability in harsh industrial environments.
Application Areas
- Bearing Temperature: Monitoring thrust and radial bearing temperatures in turbines and pumps.
- Stator Winding: Tracking the internal heat of large electric motor and generator windings.
- Exhaust Gas: Measuring gas temperatures in reciprocating engines and gas turbines.
- Process Temperature: Integrating critical static temperature points into the overall machinery protection logic.

Product Specifications
- Weight: 0.82 kg
- Dimensions: 24.1 cm x 2.4 cm x 10.3 cm
- Country of Origin: United States (USA)
- I/O Module Options: Internal Termination or External Termination
Operating Precautions
- Cold Junction Compensation: When using Thermocouples, ensure the correct I/O module is used to provide accurate Cold Junction Compensation (CJC).
- Burnout Detection: Configure the monitor’s “Sensor Failure” logic to ensure the system reacts safely (High or Low) in the event of a broken wire or open circuit.
- PWA Handling: As the 163179-01G is conformal coated, avoid using harsh chemical cleaners that may degrade the protective layer.
- Bypass Mode: Always put the monitor in “Bypass” before performing maintenance or secondary injection testing to prevent accidental machine trips caused by alarm logic.
Recommended Similar Products
| Model Number | Product Description | System Series |
|---|---|---|
| 3500/61 | Temperature Monitor w/ Recorder | 3500 Series |
| 3500/62 | Process Variable Monitor | 3500 Series |
| 133827-01 | RTD/TC I/O Module (Int. Term) | 3500/60 |
| 133819-01 | RTD/TC I/O Module (Ext. Term) | 3500/60 |
| 3500/33 | 16-Channel Relay Module | 3500 Series |