Description
Product Description
The ABB REJ525B 415BAA, article number 1MRS091415, is a combined overcurrent and earth-fault protection relay designed for medium-voltage distribution networks, utility substations, and industrial power systems. It monitors phase and neutral currents through current transformers (CTs) and initiates alarms or circuit-breaker tripping when configured protection thresholds are exceeded.
The REJ 525 provides low-set and high-set phase-overcurrent protection and low-set and high-set earth-fault protection. It features an LCD display, front-panel push buttons, status indicators, and an optically isolated serial interface for configuration and testing. This version has 1 A / 5 A rated phase-current inputs and 1 A / 5 A earth-fault current inputs. Verify the complete order code, wiring, auxiliary supply, and protection settings before installation or replacement.

Product Parameters
Brand: ABB
Model: REJ525B 415BAA
Article Number: 1MRS091415
Product Name: Combined Overcurrent and Earth-Fault Protection Relay
Product Series: REJ 525
Product Type: Secondary Protection Relay
Protection Functions: Low-set and high-set phase overcurrent; low-set and high-set earth fault
Rated Phase-Current Inputs: 1 A / 5 A
Rated Earth-Fault Current Inputs: 1 A / 5 A
Auxiliary Supply: 110–240 V AC or 48–220 V DC
Rated Frequency: 50/60 Hz
User Interface: Backlit LCD, push buttons, Ready/Start/Trip indicators
Communication Interface: Optically isolated serial PC interface; optical bus connection available through compatible accessories
Mounting Options: Flush, semi-flush, wall, side-by-side, and 19-inch rack mounting with appropriate kits
Place of Manufacture: Finland, as reported for this model by sellers; verify the individual unit label
Product Status: Confirm with seller; condition varies by listing
Dimensions: Confirm against the ABB installation drawing
Weight: Approximately 3.4 kg, reported by sellers; verify for the supplied unit
Country of Origin: Finland, subject to confirmation from the product nameplate
Power Requirements: 110–240 V AC or 48–220 V DC auxiliary supply
Discontinued: Yes. ABB lists the REJ 525 as inactive since 2011.
Recommended Models
The following ABB relays are related protection products for feeder, overcurrent, and earth-fault applications. They are not guaranteed direct replacements for REJ525B 415BAA.
- ABB REJ525B 412BAA – REJ 525 relay with 0.2 A / 1 A earth-fault inputs
- ABB REJ523 – Overcurrent and earth-fault protection relay
- ABB REJ521 – Overcurrent and earth-fault protection relay
- ABB REF615 – Feeder protection and control relay
- ABB REF620 – Feeder protection and control IED
- ABB REF630 – Feeder protection and control IED
- ABB REF610 – Feeder protection relay
- ABB REF601 – Feeder protection relay
- ABB REM615 – Motor protection and control relay
- ABB REM620 – Motor protection and control IED
- ABB RET615 – Transformer protection and control relay
- ABB RET620 – Transformer protection and control IED
- ABB REU615 – Voltage protection and control relay
- ABB REJ603 – Self-powered overcurrent protection relay
- ABB RER103 – Optical bus connection module for compatible REJ 525 installations
Q&A
Q1: What is the ABB REJ525B 415BAA used for?
A: It provides phase-overcurrent and earth-fault protection for feeders and compatible electrical distribution equipment.
Q2: What is the difference between REJ525B 415BAA and REJ525B 412BAA?
A: The 415BAA version has 1 A / 5 A earth-fault inputs, while the 412BAA version has 0.2 A / 1 A earth-fault inputs. Select the version that matches the existing CT circuit and protection design.
Q3: What auxiliary power supply does it require?
A: The specified supply options are 110–240 V AC or 48–220 V DC. Confirm the relay nameplate before connecting power.
Q4: Is the REJ 525 still an active ABB product?
A: No. ABB lists the REJ 525 as inactive since 2011. Units may still be available through spare-parts suppliers and existing inventory.
Q5: Can it directly replace another ABB protection relay?
A: Not necessarily. Check CT input ratings, protection functions, settings, terminal wiring, mounting dimensions, and communication requirements before replacement.