Sale!

WOODWARD | 5441-693 | HD Discrete I/O Field Termination Module

Original price was: $10,000.00.Current price is: $1,244.00.

Product NO:5441-693

Brand:Woodward

Delivery time:  In stock

Product status:   Brandnew

Product situation: one year warranty, Origin of Manufacture

There are still many products that have not been released yet. If you have any products that you cannot find, you can ask me for a quote! Reminder: The product images published on this website are not actual real products and are for reference only!

Description

🔹 Product Description

The Woodward 5441-693 Rev D HD Discrete I/O Field Termination Module (FTM) is an industrial input/output interface designed for Woodward MicroNet and compatible turbine control systems.

The module provides 24 discrete input connections and 12 SPDT relay outputs, allowing field signals from switches, sensors, and other discrete devices to interface with compatible control system hardware.

The 5441-693 is designed to work with the 48/24 Discrete Combo Module. Two 24/12 discrete modules can be connected to one compatible combo module to provide expanded discrete I/O capacity.

Its removable field connectors simplify wiring maintenance and module replacement. The relay arrangement also includes an I/O lockout function that can de-energize the relay outputs when the associated lockout signal is activated.

This module is suitable for turbine automation, industrial process control, generator protection interfaces, and equipment monitoring applications.

5441-693

5441-693

⚙️ Main Functions & Applications

• 24 Discrete Inputs – Accepts field input signals from compatible switches, contacts, and discrete devices.

• 12 SPDT Relay Outputs – Provides relay switching for external control circuits.

• Field Signal Interface – Connects field wiring with compatible Woodward control hardware.

• I/O Lockout Function – Supports relay de-energization through the associated I/O lockout signal.

• Removable Connectors – Simplifies field wiring inspection and maintenance.

• Replaceable Relays – Supports relay replacement and servicing.

• High-Density I/O – Provides multiple input and output connections in a compact industrial assembly.

Typical applications:

• Gas turbine control systems

• Steam turbine automation

• Generator control systems

• Industrial compressor control

• Oil and gas processing facilities

• Marine engine automation

• Industrial machinery interlocking

• Alarm and shutdown systems

 

📋 Product Datasheet & Parameters

Brand: Woodward

Model: 5441-693

Revision: Rev D

Series: Woodward MicroNet / High-Density Discrete I/O

Product Name: HD Discrete I/O Field Termination Module

Product Type: Discrete Input/Output Field Termination Module

Input Channels: 24 Discrete Inputs

Output Channels: 12 SPDT Relay Outputs

Compatible Equipment: 48/24 Discrete Combo Module

Relay Type: SPDT (Form C)

Maximum Resistive Output Ratings:

  • 10 A at 28 VDC
  • 3 A at 150 VDC
  • 10 A at 115 VAC
  • 10 A at 240 VAC

Maximum Inductive Output Ratings:

  • 3 A at 28 VDC
  • 1.2 A at 150 VDC
  • 6 A at 115 VAC
  • 3 A at 240 VAC

Connection Type: Removable Field Connectors

Mounting: DIN-Rail Mounted Assembly

Place of Manufacture: United States (reported; verify individual unit)

Product Condition: Verify actual inventory condition

Dimensions: Approximately 205 × 65 × 55 mm; verify the exact assembly configuration

Weight: Approximately 0.5–2.28 kg depending on the supplied assembly and packaging

Power Requirements: Depends on the associated MicroNet I/O architecture and field wiring; verify the system documentation

Discontinued: Current lifecycle status requires manufacturer confirmation

 

🔧 Installation & Commissioning Guide

  1. Product Identification

Verify 5441-693, Rev D, connector configuration, and the associated Woodward I/O hardware.

  1. System Shutdown

Shut down the controller according to the approved turbine or industrial equipment maintenance procedure.

  1. Power Isolation

Isolate the control system and external field circuits before disconnecting wiring.

  1. Wiring Preparation

Label all 24 discrete input connections and 12 relay output circuits before removing the original module.

  1. Module Installation

Mount the FTM securely on the designated DIN rail and check the mechanical connections.

  1. Cable Connection

Connect the appropriate MicroNet High-Density Analog/Discrete cable to the compatible 48/24 Discrete Combo Module.

  1. I/O Configuration

Verify input channel assignments, relay output mapping, and I/O lockout configuration against the original system drawings.

  1. Functional Testing

Test each input and output individually. Confirm relay switching, field signal response, and lockout operation.

  1. Final Verification

Check all system alarms and confirm that the control system recognizes the connected I/O hardware before returning equipment to service.

 

🧰 Daily Maintenance & Care

  1. Visual Inspection

Inspect the module for corrosion, damaged connectors, discoloration, and abnormal heat marks.

  1. Terminal Inspection

Check removable connectors for loose wiring, oxidation, and damaged contacts.

  1. Relay Inspection

Check relay operation and inspect for abnormal switching behavior or contact deterioration.

  1. Signal Verification

Verify discrete input signals from switches, limit devices, and field contacts.

  1. Output Testing

Perform scheduled functional tests of relay outputs according to approved maintenance procedures.

  1. Cable Maintenance

Inspect high-density cables for damaged insulation, loose connections, and mechanical stress.

  1. Lockout Function Testing

Verify the I/O lockout function according to the approved system test procedure.

  1. Environmental Maintenance

Maintain proper cabinet ventilation and prevent dust, moisture, and contamination.

  1. Spare Parts Storage

Store replacement modules in antistatic packaging in a clean, dry environment.

 

🛠️ Troubleshooting & Common Problems

Problem 1: Discrete Input Signal Not Detected

Possible Causes:
• Loose field wiring
• Incorrect input connection
• Damaged field contact
• Faulty input circuit

Solutions:
Check the field wiring, input connections, and signal source. Verify the corresponding input channel using approved diagnostic procedures.

Problem 2: Relay Output Does Not Operate

Possible Causes:
• Damaged relay
• Incorrect output wiring
• Missing control signal
• Activated I/O lockout function

Solutions:
Check the output command, relay condition, external circuit, and lockout signal. Replace faulty relays with approved compatible components.

Problem 3: Intermittent Input Signals

Possible Causes:
• Loose connectors
• Electrical interference
• Damaged cables
• Unstable field contact

Solutions:
Inspect connectors, grounding, cable routing, and field devices.

Problem 4: Multiple Relay Outputs De-Energized

Possible Causes:
• I/O lockout signal activated
• Associated DO module fault
• Control system shutdown
• Internal relay circuit problem

Solutions:
Check the I/O lockout status and associated control system diagnostics before restoring operation.

Problem 5: Communication or I/O Recognition Failure

Possible Causes:
• Incorrect high-density cable connection
• Incompatible combo module
• Loose connectors
• Incorrect system configuration

Solutions:
Verify the cable assembly, combo module compatibility, and controller configuration.

Problem 6: Relay Contact Overheating

Possible Causes:
• Excessive electrical load
• Incorrect load classification
• Loose terminal connections
• Relay contact deterioration

Solutions:
Check the actual load current and voltage against the specified resistive or inductive ratings. Replace damaged components.

Problem 7: Replacement Module Does Not Match Original

Possible Causes:
• Revision mismatch
• Incorrect connector arrangement
• Different I/O configuration
• Incompatible host equipment

Solutions:
Confirm the complete part number 5441-693, revision, terminal mapping, and associated I/O hardware before installation.

 

⚠️ Safety Precautions

• Disconnect electrical power before installing or removing the module.

• Isolate external field circuits before servicing terminals.

• Follow industrial lockout/tagout procedures.

• Verify voltage and current ratings before connecting relay loads.

• Never exceed the specified resistive and inductive contact ratings.

• Use ESD protection when handling electronic assemblies.

• Never assume that similar Woodward FTM models have identical wiring arrangements.

• Verify I/O lockout operation before returning the equipment to service.

• The 24/12 discrete relay module is intended for ordinary, non-hazardous locations; observe the applicable installation restrictions.

• Installation and commissioning should be performed by qualified industrial automation technicians.

 

❓ Frequently Asked Questions

Q1: What is Woodward 5441-693?

A: It is a high-density discrete I/O Field Termination Module used with compatible Woodward control system hardware.

Q2: How many input and output channels does it provide?

A: It provides 24 discrete input connections and 12 SPDT relay outputs.

Q3: Which module does it work with?

A: It is designed for use with the compatible 48/24 Discrete Combo Module.

Q4: Does it contain relay outputs?

A: Yes. It incorporates 12 SPDT relay outputs with specified resistive and inductive load ratings.

Q5: What is the purpose of the I/O lockout function?

A: It allows the associated lockout signal to de-energize the relay outputs.

Q6: Are the field connectors removable?

A: Yes. Removable connectors simplify field wiring maintenance and replacement.

Q7: Can it replace Woodward 5441-694?

A: Not automatically. The 5441-694 has a different relay-driver output configuration. Verify the complete system design before considering substitution.

Q8: What should be checked before purchasing?

A: Confirm model 5441-693, revision D, input/output configuration, connector condition, and compatibility with the installed Woodward control system.

 

📦 Recommended Woodward Models

The following 15 Woodward products are related to industrial turbine control, MicroNet automation, and discrete I/O applications. They are not all direct replacements for 5441-693.

  1. Woodward 5441-694 – HD Discrete I/O FTM, 24 Inputs / 12 Relay Drivers
  2. Woodward 5441-413 – Discrete Output Relay Module, 32 Channels
  3. Woodward 5441-419 – Discrete Output Relay Module, 16 Channels
  4. Woodward 5501-367 – High-Density Discrete I/O Module
  5. Woodward 5453-276 – TMR Discrete I/O Module
  6. Woodward 5466-1000 – MicroNet Control Module
  7. Woodward 5466-1145 – MicroNet I/O Module
  8. Woodward 5466-1215 – MicroNet Digital I/O Module
  9. Woodward 5466-1245 – CPU5200 Enhanced Performance Module
  10. Woodward 5466-1246 – MicroNet Remote RTN Module
  11. Woodward 5466-353 – MicroNet Control Module
  12. Woodward 9907-164 – 505 Digital Turbine Control
  13. Woodward 9907-167 – 505 Digital Turbine Control
  14. Woodward 8200-1200 – LINKnet HT RTD Input Module
  15. Woodward 8200-1202 – LINKnet HT 4–20 mA I/O Module

Woodward automation products are widely used in turbine control, generator automation, industrial engine management, compressor control, and power generation systems.

about us

At Newplcdcs, we specialize in providing high-quality spare parts for Distributed Control Systems (DCS) and Programmable Logic Controllers (PLC). Our comprehensive product portfolio includes parts from approximately 20 leading brands, such as ABB, Bently Nevada, Honeywell, GE, Yokogawa, Allen Bradley, Foxboro, Ovation, Hima, Emerson, Triconex, Woodward, ICS Triplex, Bachmann, and Schneider. This focused expertise allows us to offer in-depth solutions in the automation sector, setting us apart from many competitors and ensuring we deliver the most advanced and reliable products to our clients.

Contact Information

Frequently Asked Questions
Is our price competitive?
Newsplcdcs collaborates with over 50 countries worldwide. as a leading supplier in china, we can provide significant discounts to customers based on market demand.
What is the warranty period?
We offer a standard one-year warranty for all new and original items.
What payment methods do we accept?
We accept 100% t/t (telegraphic transfer) before shipping. for items with a lead time, a 30% deposit is required in advance, with the remaining 70% balance due before shipping. if you have an agent in china, please contact us for rmb transfer.
What shipping methods do we use?
We primarily utilize carriers such as fedex, dhl, ups, bre, etc. if you have an account with any of these carriers, you can arrange the shipping yourself. additionally, we offer free shipping to china freight forwarders.
What is our delivery time?
Typically, delivery takes around 1-3 days after receiving the advance payment. for items with a quoted lead time, delivery will occur as per the specified lead time.
How do we package the goods?
Our packaging process involves multiple layers of protection. initially, the product is placed in its original box, sealed with a label. then, we add a layer of bubble wrap to safeguard against collisions during transportation. finally, all products are securely packed in sturdy boxes for further protection.
How can customers contact us and request a quote?
Customers can inquire via email, whatsapp, wechat, skype, or any preferred communication platform. simply reach out to us, and we’ll promptly provide a quote tailored to your needs.