Product Description
The General Electric SKLL36AT0800 is a three-pole, 800 A molded case circuit breaker from the GE Spectra RMS SKL series, designed for industrial and commercial three-phase power distribution systems. It features a 600 VAC maximum voltage rating, an 800 A frame rating, and a solid-state electronic RMS-sensing trip system. The SKL breaker uses an interchangeable rating plug to establish the applicable ampere rating and provides LSI protection, including long-time, short-time, and instantaneous trip functions. Its SKL frame designation corresponds to a 65 kA interrupting rating at 480 VAC under the applicable UL 489 rating conditions. The breaker is 100% rated under its specified UL configuration and is suitable for reverse-feed applications. It is commonly used in industrial switchboards, power distribution assemblies, and large feeder protection systems. Before installation, verify the rating plug, trip-unit configuration, fault-current level, bus arrangement, terminal lug requirements, and switchboard compatibility. This breaker is a specialized high-current protective device and should be installed and commissioned by qualified electrical personnel.

📋 Product Specifications
- Brand: General Electric (GE)
- Model: SKLL36AT0800
- Product Series: Spectra RMS / SKL
- Product Name: 800 A Electronic Trip Molded Case Circuit Breaker
- Product Type: Solid-State Electronic Molded Case Circuit Breaker
- Frame Rating: 800 A
- Rated Current: 800 A maximum sensor rating; actual ampere setting depends on the installed rating plug
- Number of Poles: 3
- Rated Voltage: 600 VAC maximum
- Interrupting Rating: 65 kA at 480 VAC (UL 489)
- Protection Functions: LSI – Long-Time, Short-Time, Instantaneous
- Trip Technology: Digital solid-state RMS sensing
- Rating Plug: Interchangeable; compatible 800 A frame rating plugs include SRPK800A300 through SRPK800A800
- Current Sensor: 800 A
- Continuous Current Rating: 100% UL rated under specified installation conditions
- Mounting: Bolt-on
- Reverse Feed: Suitable, subject to approved installation requirements
- Terminal Lug Accessory: TCAL81; verify whether included
- Compatible Conductor Range: Three 3/0–500 kcmil copper or aluminum conductors with the specified TCAL81 lug arrangement
- Place of Manufacture: Not officially confirmed for the individual unit
- Country of Origin: Verify product nameplate
- Dimensions: Exact manufacturer dimensions not confirmed; verify switchboard drawings
- Weight: Approximately 45–57 lb (20.4–25.9 kg), depending on catalog or shipping configuration
- Power Requirements: No separate control supply required for the standard electronic trip configuration; verify installed accessories
- Product Status: Legacy Spectra RMS product
- Discontinued: Current manufacturer lifecycle status not officially confirmed
🏭 Application Areas
- Industrial three-phase power distribution
- Main and feeder circuit protection
- Manufacturing plant switchboards
- Commercial electrical distribution systems
- Power generation auxiliary distribution
- Large industrial equipment protection
- GE Spectra-compatible switchboard maintenance and replacement
🔧 Installation and Operating Instructions
1. Pre-Installation Inspection
Verify the complete catalog number SKLL36AT0800. Inspect the breaker housing, operating handle, terminals, trip unit, rating plug, and mounting surfaces. Confirm the 800 A frame rating, 600 VAC maximum voltage, three-pole configuration, and 65 kA interrupting rating at 480 VAC.
2. Rating Plug Verification
The SKL frame uses interchangeable rating plugs to establish the applicable ampere rating. Compatible rating plug references include SRPK800A300, SRPK800A400, SRPK800A500, SRPK800A600, SRPK800A700, and SRPK800A800. Confirm the installed rating plug and intended protection setting before energization. Do not assume that an 800 A frame automatically provides an 800 A continuous trip setting.
3. Electrical Isolation
Disconnect all upstream power sources and apply the site’s lockout/tagout procedure. Verify the absence of voltage using appropriately rated test equipment. Check for alternate power feeds and stored electrical energy before handling the breaker.
4. Mechanical Installation
Confirm that the switchboard is designed for the GE Spectra SKL frame. Align the breaker with the approved mounting arrangement and secure it using the specified hardware. Check mechanical operation and verify that the breaker is properly seated. Do not force the breaker into an incompatible enclosure.
5. Terminal Connections
The TCAL81 lug assembly is a relevant front-connection accessory for this frame. It accommodates three 3/0–500 kcmil copper or aluminum conductors in the documented configuration. Confirm the actual lug kit, conductor material, conductor size, and terminal torque specifications before connection. Do not assume that lugs are included with the breaker.
6. Power-On Sequence
Complete mechanical and electrical inspections before restoring power. Verify phase connections, conductor termination, insulation clearances, protective settings, and switchboard assembly. Energize the equipment according to the approved commissioning procedure and monitor for abnormal temperature, noise, or protective-device indications.
7. Normal Operation
During operation, the breaker provides long-time protection against sustained overloads, short-time protection for time-delayed fault coordination, and instantaneous protection for high-current faults. Monitor load current and trip indications. Investigate any unexpected trip before attempting to reset the breaker.
8. Parameter and Protection Setting
The solid-state RMS trip system uses the interchangeable rating plug and the applicable trip-unit adjustment features. Set long-time, short-time, and instantaneous protection according to the approved coordination study and GE instructions. Do not select settings solely from the frame rating or connected load estimate.
9. Shutdown and Removal
Open the breaker using the approved switching procedure, isolate all upstream sources, apply lockout/tagout, and verify the absence of voltage. Disconnect conductors only after confirming safe conditions. Record the rating plug, trip settings, and accessory configuration before removal.
🧰 Daily Maintenance
- Inspect the breaker housing for cracks, deformation, or signs of overheating.
- Check the operating handle and mechanical mechanism for abnormal movement.
- Inspect terminal connections during scheduled outages.
- Verify the installed rating plug and protection settings.
- Review trip history and investigate repeated overload or fault events.
- Check bus connections and mounting hardware for deterioration.
- Perform manufacturer-approved electrical and mechanical inspections.
- Keep the switchboard clean, dry, and adequately ventilated.
- Record inspection results, trip events, and maintenance actions.
⚠️ Troubleshooting
Problem 1: Breaker trips under normal operating load
Measure actual load current and verify the installed rating plug and long-time protection setting. Check for overloads, phase imbalance, and incorrect coordination.
Problem 2: Breaker trips immediately after closing
Treat this as a possible short circuit or serious downstream fault. Keep the equipment isolated until the fault is located and corrected. Do not repeatedly attempt to close the breaker.
Problem 3: Breaker will not close
Check the operating mechanism, reset condition, mechanical interlocks, and switchboard mounting arrangement. Inspect for physical damage or obstruction.
Problem 4: Excessive terminal temperature
Isolate the equipment and inspect conductor sizing, lug compatibility, terminal torque, and contact condition. Replace damaged components using approved parts.
Problem 5: Protection does not operate as expected
Verify the rating plug, trip-unit condition, long-time and short-time settings, instantaneous setting, and protection coordination. Arrange appropriate testing by qualified personnel.
Problem 6: Breaker cannot be installed in the existing panel
Check the frame type, mounting arrangement, bus connection, and enclosure design. Do not modify the breaker or switchboard to force compatibility.
🛡️ Safety Precautions
- Installation and maintenance must be performed by qualified electrical personnel.
- Always isolate power and verify the absence of voltage before servicing.
- Follow lockout/tagout and arc-flash protection procedures.
- Use PPE appropriate to the electrical hazard assessment.
- Never exceed the rated voltage or interrupting capacity.
- Do not bypass trip functions or install an incompatible rating plug.
- Confirm lug compatibility and terminal torque before energization.
- Do not repeatedly reset a breaker after an unexplained trip.
- Verify fault-current levels and protective coordination before commissioning.
❓ Frequently Asked Questions
Q1: What is the GE SKLL36AT0800?
It is an 800 A, three-pole Spectra RMS electronic molded case circuit breaker.
Q2: What is its maximum rated voltage?
The catalog rating is 600 VAC maximum.
Q3: What is its interrupting capacity?
The SKL version is rated at 65 kA at 480 VAC under the applicable UL 489 conditions.
Q4: What does LSI protection mean?
LSI refers to Long-Time, Short-Time, and Instantaneous overcurrent protection.
Q5: Is this breaker 100% rated?
Yes. The GE catalog identifies the applicable SKL configuration as 100% UL rated, subject to specified installation and conductor requirements.
Q6: Does it include terminal lugs?
The TCAL81 is the associated front-connection lug accessory. Confirm whether it is included with the actual item.
Q7: Can the breaker be reverse-fed?
The product documentation identifies the SKL frame as suitable for reverse-feed applications. Confirm the specific installation requirements before use.
Q8: Can it replace another GE Spectra breaker?
Not automatically. Verify frame rating, interrupting capacity, pole count, rating plug, trip functions, mounting, and bus connections.
🔗 Related General Electric Models and Components
The following models and accessories belong to or are associated with the GE Spectra RMS circuit breaker family. They are related products, not all direct replacements for SKLL36AT0800.
- SKHH36AT0800 – Spectra SKH 800 A, 3-pole breaker, 50 kA class at 480 VAC
- SKPP36AT0800 – Spectra SKP 800 A, 3-pole breaker, 100 kA class at 480 VAC
- SKLL36AT0800 – Spectra SKL 800 A, 3-pole breaker, 65 kA class at 480 VAC
- SRPK800A300 – 300 A rating plug for 800 A sensor frame
- SRPK800A400 – 400 A rating plug for 800 A sensor frame
- SRPK800A500 – 500 A rating plug for 800 A sensor frame
- SRPK800A600 – 600 A rating plug for 800 A sensor frame
- SRPK800A700 – 700 A rating plug for 800 A sensor frame
- SRPK800A800 – 800 A rating plug for 800 A sensor frame
- TCAL81 – Front-connection copper/aluminum terminal lug kit
- SKHH36AT1200 – Spectra SKH 1200 A breaker variant
- SKLL36AT1200 – Spectra SKL 1200 A breaker variant
- SKPP36AT1200 – Spectra SKP 1200 A breaker variant
- SG600 Series – GE Spectra RMS molded case breaker family
- SK1200 Series – GE Spectra RMS high-current breaker family
Ordering Note: Verify the full catalog number, frame rating, rating plug, trip functions, interrupting capacity, terminal lug requirements, and switchboard compatibility before ordering. Confirm the actual product condition, included accessories, and test status against the physical unit.