1. Product Description
The Bihl+Wiedemann BWU2634 is an ASi-3 PROFINET gateway with an integrated Safety Monitor and two ASi master channels. It connects two ASi networks to a higher-level PROFINET automation system while providing integrated safety monitoring, local digital inputs, and electronic safety outputs. The gateway supports three dual-channel safety input groups, six digital inputs, and six electronic safety output circuits. Its Safe Link function supports safety communication between compatible devices, while duplicate-address recognition and ASi fault detection simplify network diagnostics. The BWU2634 supports applications up to SIL 3, Performance Level e, and Category 4 when correctly designed, configured, and validated as part of the complete safety system. It is suitable for industrial machinery, automated production lines, and safety-related control installations that require ASi-3 field-device integration with PROFINET communication.

2. Key Technical Specifications
- Brand: Bihl+Wiedemann
- Model: BWU2634
- Product Series: ASi-3 Safety Gateway
- Product Type: PROFINET Gateway with Integrated Safety Monitor
- ASi Standard: ASi-3
- Number of ASi Masters: 2
- Number of ASi Networks: 2
- Fieldbus Interface: PROFINET IO Device
- PROFINET Ports: 2 x RJ45 with integrated 2-port switch
- PROFINET Functions: MRP and Shared Device; IRT capability listed in manufacturer documentation
- Safety Communication: Safe Link
- Local Safety Inputs: 3 x 2-channel
- Local Digital Inputs: Up to 6, including EDM functionality
- Integrated Safety Outputs: 6 electronic safety outputs
- Expandable Safety Inputs: Up to 62 x 2-channel inputs per applicable system configuration
- Expandable Safety Outputs: Up to 32 safety outputs per applicable system configuration
- AUX Supply Voltage: 24 VDC (19.2–28.8 V)
- Maximum AUX Current Consumption: 7.2 A
- ASi Current Limit: Maximum 4 A per ASi network
- Diagnostic Interface: PROFINET and RS232
- Protection Rating: IP20
- Safety Capability: Up to SIL 3 / Category 4 / PL e, subject to system design and validation
- Connection Type: COMBICON
- Dimensions: Not independently confirmed for this exact unit
- Weight: Not independently confirmed
- Country of Origin: Germany (manufacturer location; verify the individual unit label)
- Product Lifecycle: Successor model BWU3274 is listed by the manufacturer; verify spare-part suitability before substitution
3. Application Scenarios
- Industrial automation: Connects ASi field devices to PROFINET-based PLC control systems.
- Packaging machinery: Integrates emergency stops, safety switches, and protective devices into machine safety circuits.
- Automotive production: Supports safety-related monitoring across automated assembly and handling equipment.
- Conveyor systems: Connects distributed ASi sensors and safety devices across production lines.
- Material handling: Provides safety monitoring for access doors, protective guards, and emergency-stop circuits.
- Process machinery: Integrates safety-related field signals with higher-level automation.
- Machine modernization: Supports migration or maintenance projects involving existing ASi-3 networks and PROFINET controllers.
4. Installation and Operating Procedure
- Verify the complete BWU2634 model identification and inspect the device label.
- Confirm compatibility with the existing PROFINET controller, ASi-3 devices, and safety architecture.
- Review the network topology, ASi address plan, safety configuration, and approved wiring diagrams.
- Isolate the relevant power sources and apply lockout/tagout procedures.
- Mount the gateway in an appropriate control cabinet and maintain the required ventilation and environmental conditions.
- Connect both ASi networks using the designated terminals and approved wiring.
- Connect the 24 VDC AUX supply, observing polarity and the specified voltage range.
- Connect the PROFINET network through the RJ45 interfaces.
- Wire the local safety inputs and electronic safety outputs according to the approved circuit design.
- Configure the gateway and Safety Monitor using the applicable Bihl+Wiedemann engineering software.
- Import or verify the correct device description and configure the PROFINET controller.
- Check ASi addressing, duplicate-address diagnostics, network status, and safety-device communication.
- Perform the approved functional tests for all safety inputs and outputs.
- Document commissioning results and obtain authorization before returning the machine to operation.
5. Configuration and System Integration
The BWU2634 integrates two ASi-3 master networks with a PROFINET-based automation system. It includes an integrated Safety Monitor and supports Safe Link safety communication.
Configuration and integration considerations:
- Configure the PROFINET device name and network parameters according to the PLC project.
- Verify the controller’s device description and process-data mapping.
- Assign unique addresses to all ASi nodes.
- Configure the two ASi master networks independently according to the system design.
- Set up local digital and safety input functions.
- Configure the six electronic safety output circuits according to the approved safety logic.
- Verify Safe Link communication with compatible safety devices.
- Use the manufacturer’s engineering software for diagnostics and safety configuration.
- Confirm that the AUX supply can support the connected loads within its specified current limits.
The manufacturer lists two RJ45 PROFINET ports, an integrated 2-port switch, MRP, and Shared Device functionality. Do not assume that every network redundancy or controller feature is enabled in the existing PLC project; confirm the supported configuration before commissioning.
6. Daily Maintenance and Inspection
- Inspect the gateway housing and terminals for damage, dust, and contamination.
- Check the 24 VDC supply and AUX wiring.
- Inspect PROFINET cables and RJ45 connectors for damage or loose connections.
- Review ASi network diagnostics and communication status.
- Check for duplicate ASi addresses and ASi line faults.
- Inspect field-device wiring and safety input connections.
- Verify that safety output circuits operate according to the approved maintenance procedure.
- Keep the cabinet within the specified operating environment.
- Maintain backups of safety configuration, gateway parameters, and PLC project files.
- Perform periodic safety-function testing according to the plant’s approved maintenance schedule.
7. Troubleshooting Guide
Problem: PROFINET communication failure.
- Check the RJ45 cables and network connections.
- Verify the device name and IP configuration.
- Review the PLC hardware configuration and device diagnostics.
- Check the network switch and MRP configuration where applicable.
Problem: ASi network communication fault.
- Check the ASi power supply and wiring.
- Verify node addresses and network connections.
- Investigate duplicate-address warnings.
- Review ASi fault detector diagnostics for interference or external voltage.
Problem: Safety input is not recognized.
- Check the input wiring and connected safety device.
- Verify the configured input channel arrangement.
- Review the Safety Monitor configuration.
- Perform the approved safety input test.
Problem: Safety output does not switch.
- Check the safety logic and release conditions.
- Inspect the output wiring and connected load.
- Verify the AUX supply and output loading.
- Review the gateway diagnostics and safety configuration.
Problem: Gateway does not start correctly.
- Verify the 24 VDC AUX supply is within specification.
- Check polarity, terminal connections, and power loading.
- Inspect the gateway for physical damage.
- Review diagnostic indicators and manufacturer troubleshooting instructions.
8. Safety Precautions
- Installation and commissioning must be performed by qualified industrial automation and functional-safety personnel.
- Isolate electrical supplies and apply lockout/tagout procedures before wiring or maintenance.
- Do not exceed the specified AUX supply voltage or ASi network current limits.
- Do not bypass safety inputs, force safety outputs, or disable protective functions.
- Verify the complete safety circuit after any wiring or configuration change.
- Confirm the required SIL, PL, and Category ratings through a system-level risk assessment and validation.
- Use only approved safety configuration procedures and retain configuration records.
- Do not replace the BWU2634 with another gateway based solely on a similar product description or number of ASi masters.
9. Related Bihl+Wiedemann Models
The following models belong to related Bihl+Wiedemann ASi gateway and safety-monitor product families. They are useful for system comparison and spare-part identification, but they are not automatically interchangeable with BWU2634.
- BWU2633 – ASi-3 PROFINET gateway variant.
- BWU2642 – ASi-3 PROFINET gateway with integrated Safety Monitor and mixed relay/electronic safety outputs.
- BWU3274 – Successor model to BWU2634.
- BWU3080 – ASi-3 PROFINET safety gateway with redundant supply architecture.
- BWU3692 – ASi-3 PROFINET safety gateway with one ASi master.
- BWU2307 – ASi-3 PROFINET gateway with integrated Safety Monitor.
- BWU2798 – ASi-3 PROFINET safety gateway variant.
- BWU2828 – ASi-3 PROFINET safety gateway variant.
- BWU3952 – Successor model listed for BWU2642.
- BWU3000 – ASi-3 safety demonstration and starter system.
- BWU2634 – ASi-3 dual-master PROFINET safety gateway.
- BWU3274 – Dual-master ASi-3 PROFINET safety gateway.
- BWU2642 – Dual-master ASi-3 PROFINET safety gateway with four release circuits.
- BWU3080 – Dual-master ASi-3 PROFINET safety gateway with redundant supply.
- BWU3692 – Single-master ASi-3 PROFINET safety gateway.
For replacement selection, compare the number of ASi masters, safety input channels, output type, supply architecture, communication interface, and safety configuration.
10. Product Verification and Purchasing Notes
Before purchasing, request clear photographs of the actual BWU2634 unit, including the front label, model number, terminal connections, RJ45 ports, and condition of the housing. Confirm whether the unit is new surplus, unused, refurbished, or previously installed. Ask whether functional testing has been completed and whether a test report is available.
Important interface clarification: the manufacturer’s official documentation identifies BWU2634 as a PROFINET gateway. If the existing installation requires PROFIBUS, verify the required gateway model before ordering. Do not rely on the eBay title alone.
Bihl+Wiedemann lists BWU3274 as the successor to BWU2634, but the manufacturer specifically cautions that the successor is not recommended automatically as a spare-part replacement. Confirm the required hardware, wiring, configuration, and application compatibility before considering a substitution.