Product Introduction
The GENERAL ELECTRIC DS200SLCCG3A is a LAN Communication Card designed for GE Mark V and EX2000 industrial control systems. Identified by the functional acronym SLCC, this board contains a LAN Control Processor (LCP) that manages communication signals exchanged between the controller and associated drive or turbine-control hardware. It includes isolated and non-isolated communication circuits, replaceable EPROM program memory, dedicated RAM, and dual-port RAM for communication with the Drive Control Processor on the DS215SDCC board. The board also features a 16-position alphanumeric display and an interface for an attachable programmer keypad, supporting diagnostic testing, fault-code readout, and approved software adjustments. It is used in legacy GE control installations where the original communication architecture and hardware configuration must be maintained.

Product Parameters
- Brand: General Electric (GE)
- Model: DS200SLCCG3A
- Series: GE Mark V / EX2000 / DC2000
- Product Name: LAN Communication Card
- Functional Acronym: SLCC
- Product Type: Industrial Communication and Processor Board
- Main Processor: LAN Control Processor (LCP), U1
- Program Memory: Replaceable EPROMs at U6 and U7
- Dedicated RAM: U8 and U9
- Dual-Port RAM: U5
- Display: 16-position alphanumeric display
- Display Controller: U18
- Programmer Interface: KPPL connector
- Communication Interface: 3PL interface to the SDCC processor
- Board Connection: 2PL connector
- Compatible Platforms: GE Mark V and EX2000; verify exact cabinet configuration
- Board Group: G3
- Hardware Revision: A
- Total Plug Connectors: 5, supplier-listed specification
- I/O Connectors: 4, supplier-listed specification
- Power Connectors: 1, supplier-listed specification
- Place of Manufacture: Not independently verified; check the board label
- Country of Origin: Confirm from the individual unit’s nameplate
- Dimensions: Standard GE Mark V board format; exact measurements not reliably published
- Weight: Not reliably verified; confirm before shipment
- Power Requirements: Supplied through the compatible control-system architecture; verify OEM electrical documentation
- Product Status: Legacy GE control hardware
- Discontinued: Confirm current OEM lifecycle status
- Condition: Confirm actual board condition, EPROM availability, and test status before purchase
Technical Features
- LAN Communication Processing
The onboard LAN Control Processor (U1) handles communication processing for the associated GE control system. - Isolated and Non-Isolated Circuits
Provides both isolated and non-isolated communication circuits for controller interfaces. - EPROM Program Memory
Uses replaceable EPROM devices at U6 and U7 to store the LCP software. - Dedicated RAM Architecture
Dedicated RAM devices U8 and U9 support the LAN Control Processor. - Dual-Port Memory Communication
Dual-port RAM U5 provides a shared-memory interface between the LCP and the Drive Control Processor on the DS215SDCC board through the 3PL connection. - Operator Display
Includes a 16-position alphanumeric display controlled by U18 for status and diagnostic information. - Programmer Keypad Interface
The KPPL connector supports an attachable programmer module for approved software adjustments and diagnostic operations. - Multi-Board System Integration
Interfaces with associated NTB/3TB, SDCC, TCCB, and DCFB hardware through designated board connections. - Legacy Drive and Turbine Applications
Supports maintenance of existing GE Mark V, EX2000, and related DC2000 installations, subject to the correct hardware configuration.
Operating Procedures
⚠️ Installation, testing, and maintenance should be performed by qualified industrial control technicians. Follow the applicable GE manuals, site electrical safety rules, and lockout/tagout procedures.
1. Pre-Installation Inspection
- Confirm the complete part number DS200SLCCG3A.
- Verify the G3 group and Revision A identification.
- Record the serial number and any EPROM labels or firmware identification.
- Compare the replacement board with the original installed card.
- Inspect the PCB for cracks, corrosion, damaged components, and contamination.
- Check the connector pins and board mounting points.
- Verify the presence and correct location of the U6 and U7 EPROM devices.
- Confirm compatibility with the installed SDCC, terminal, and interface boards.
- Review the relevant GEI-100162 and GEH-6005 documentation.
2. Startup and Power-On Sequence
- Place the control system in the approved maintenance or startup condition.
- Confirm that the board is installed in the correct position.
- Verify the 2PL and 3PL connections and all associated interface connections.
- Confirm that the required EPROM devices are correctly installed.
- Check the programmer module connection, if used.
- Restore cabinet power according to the approved GE procedure.
- Observe the alphanumeric display during initialization.
- Review available board and system diagnostic indications.
- Verify communication with the associated SDCC and other connected control hardware.
- Confirm normal system status before returning the equipment to service.
3. Normal Operation
- Monitor the communication status through the approved control-system interface.
- Observe the SLCC display for status messages and diagnostic codes.
- Check communication between the LAN Control Processor and the associated drive controller.
- Review communication-related alarms and system event records.
- Verify that the connected control boards respond as expected.
- Record recurring faults and abnormal diagnostic indications.
- Avoid changing communication or control settings without engineering authorization.
4. Parameter Configuration and Modification
The DS200SLCCG3A supports approved diagnostic and software adjustment functions through its programmer interface. Actual parameters depend on the installed drive or turbine-control application and firmware.
- Identify the installed board revision and EPROM configuration.
- Connect the compatible programmer module through the KPPL interface, where required.
- Record the existing configuration before making changes.
- Review the applicable GE software and system documentation.
- Modify only parameters authorized for the installed application.
- Verify the configuration against the system drawings and engineering records.
- Save approved changes using the documented procedure.
- Review diagnostic messages and confirm normal communication after modification.
⚠️ Do not exchange EPROMs between different SLCC groups or firmware configurations without confirming compatibility.
5. Shutdown Sequence
- Place the associated drive or turbine control system in the approved shutdown or maintenance state.
- Confirm that removing the SLCC will not interrupt active control or protection functions.
- Follow the site’s lockout/tagout procedure.
- Verify the required electrical safe condition before handling the board.
- Record all board connections and EPROM identification details.
- Disconnect the programmer module, if fitted.
- Remove the board using the specified extraction procedure.
- Protect the board and its EPROM devices with antistatic packaging.
- Document the removed board’s revision and firmware configuration.
Daily Maintenance
- Inspect the board for dust, moisture, corrosion, and overheating.
- Check that all connectors remain properly seated.
- Review the display for recurring diagnostic messages.
- Monitor communication faults involving the LAN Control Processor.
- Check the condition and seating of the U6 and U7 EPROM devices during scheduled maintenance.
- Verify that the programmer interface is protected from contamination.
- Maintain appropriate cabinet temperature and ventilation.
- Record recurring communication alarms and maintenance actions.
- Store spare boards in ESD-safe packaging.
Troubleshooting
Problem 1: No Display or Abnormal Display Indications
Possible causes:
- Control-system power problem
- Board not properly seated
- Display controller fault
- Board hardware failure
Recommended checks:
- Verify the control-system power supply.
- Inspect the board connectors.
- Review initialization diagnostics.
- Have the board tested by a qualified repair facility if the problem persists.
Problem 2: LAN Communication Failure
Possible causes:
- LCP processor fault
- Incorrect EPROM configuration
- Loose board connection
- Fault in associated communication hardware
Recommended checks:
- Inspect the board and associated connectors.
- Verify the U6 and U7 EPROM identification.
- Review communication diagnostic messages.
- Check related NTB/3TB, SDCC, TCCB, and DCFB hardware.
Problem 3: Communication Failure with the SDCC
Possible causes:
- 3PL interface connection problem
- Dual-port RAM fault
- SDCC hardware or processor issue
- Incompatible board revision
Recommended checks:
- Inspect the 3PL interface.
- Verify the correct SDCC board configuration.
- Review the relevant diagnostic codes.
- Check the associated control hardware before replacing the SLCC.
Problem 4: Programmer Module Not Responding
Possible causes:
- KPPL connector problem
- Programmer module fault
- Incorrect interface installation
- Board hardware fault
Recommended checks:
- Inspect the KPPL connector.
- Verify the programmer module’s compatibility.
- Check the module connection and system diagnostics.
- Use the approved GE diagnostic procedure.
Problem 5: Intermittent Communication Alarms
Possible causes:
- Poor connector contact
- Electrical noise or grounding issues
- Aging electronic components
- Related network or control-board fault
Recommended checks:
- Review the alarm history and timing.
- Inspect wiring, shielding, and grounding.
- Check the associated communication hardware.
- Perform qualified board-level testing if necessary.
Frequently Asked Questions
Q1: What is the GE DS200SLCCG3A?
It is a LAN Communication Card used in GE Mark V and EX2000 control systems.
Q2: What does SLCC stand for?
SLCC is the functional acronym used for the LAN Communications Card.
Q3: Which processor does the board use?
It uses an onboard LAN Control Processor identified as U1.
Q4: Where is the program memory located?
The LCP program software is stored in replaceable EPROM devices at U6 and U7.
Q5: Does the board have a display?
Yes. It includes a 16-position alphanumeric display controlled by U18.
Q6: Can the programmer module be connected directly to the board?
Yes. The programmer module mounts on the SLCC and connects through the KPPL interface.
Q7: Which board communicates with the SLCC through dual-port RAM?
The DS215SDCC Drive Control Card communicates with the SLCC through the U5 dual-port RAM and 3PL interface.
Q8: Is DS200SLCCG3A interchangeable with DS200SLCCG3ACC?
Do not assume automatic interchangeability. Revision compatibility and EPROM requirements must be checked against the applicable GE documentation.
Safety Precautions
⚠️ Isolate equipment according to approved procedures before removing or installing the board.
⚠️ Use ESD protection when handling the PCB and EPROM devices.
⚠️ Verify board group, revision, and firmware configuration before replacement.
⚠️ Never remove or exchange EPROM devices while the board is energized.
⚠️ Do not change communication or drive-control parameters without engineering authorization.
⚠️ Confirm normal communication and diagnostic status before returning the equipment to operation.
Recommended Related GE Models
The following models are related GE Mark V, EX2000, or DC2000 control and communication components. They are useful for spare-parts planning but are not all direct replacements for DS200SLCCG3A.
- GE DS200SLCCG1A – LAN Communication Card
- GE DS200SLCCG3ACC – LAN Communication Card, Revision Variant
- GE DS200SLCCG3AFG – LAN Communication Card Assembly Variant
- GE DS215SLCCG1AZZ01A – SLCC LAN Communication Board Assembly
- GE DS215SLCCG1AZZ01B – SLCC Communication Board Variant
- GE DS215SLCCG2AZZ01A – SLCCG2 Communication Board Assembly
- GE DS215SDCCG1AZZ01A – SDCC Drive Control Board Assembly
- GE DS200SDCCG1A – SDCC Drive Control Card
- GE DS200SDCCG4A – SDCC Drive Control Card
- GE DS200SPCBG1A – Signal Processor Board
- GE DS200TCCBG1A – Contact Input/Output Terminal Board
- GE DS200TBCBG1A – Contact Terminal Board
- GE DS200DCFBG1A – DC Feedback Board
- GE DS200TCQBG1B – Analog I/O Board
- GE DS200CDBAG1A – Communication and Drive Control Board
Compatibility Note: These models belong to related GE industrial drive and turbine-control hardware families, but they perform different functions and may have different firmware or connector configurations. Verify the exact system application, revision, EPROM configuration, and approved replacement documentation before ordering.