Product Description
The Bosch Rexroth VT-HNC100-1-20a/W-08-P-0 (R900958999 / 090958999) is a programmable digital hydraulic axis controller designed for closed-loop motion control of hydraulic drives. Part of the VT-HNC100 series, this controller is configured for one hydraulic axis, wall mounting, eight digital inputs/outputs, and PROFIBUS DP communication. It supports precision positioning, pressure and force regulation, position-dependent braking, and programmable motion sequences for industrial hydraulic applications. The controller interfaces with proportional or servo valves, position transducers, and pressure or force feedback devices to coordinate hydraulic actuator movement. Typical applications include hydraulic presses, plastic processing machinery, machine tools, steel production equipment, and automated material handling systems. Its WIN-PED engineering environment supports parameter configuration, NC program development, diagnostics, and commissioning. When replacing an existing unit, verify the complete type code, hardware revision, PROFIBUS configuration, feedback interface, wiring, and control parameters before installation.

📋 Product Datasheet
| Parameter | Specification |
|---|---|
| Brand | Bosch Rexroth |
| Model | VT-HNC100-1-20a/W-08-P-0 |
| Material Number | R900958999 |
| Alternative Part Number | 090958999 |
| Series | VT-HNC100 |
| Product Name | Digital Hydraulic Axis Controller |
| Axis Configuration | 1 Hydraulic Axis |
| Component Series | 2X / Series 20–29 |
| Mounting Type | Wall Mounting |
| Digital I/O | 8 Digital Inputs/Outputs |
| Communication | PROFIBUS DP |
| Operating Voltage | 18–36 V DC |
| Processor | 16/32-bit MC68376 |
| Analog Interface | Voltage/current signal interfaces, depending on configuration |
| Dimensions | Approx. 71 × 155 × 192 mm; verify mounting drawing and variant |
| Weight | Approx. 1.0 kg |
| Country of Origin | Germany (manufacturer headquarters; unit origin requires label verification) |
| Product Status | Used / surplus condition subject to seller confirmation |
| Discontinued | Yes; listed as discontinued |
⚙️ Operating Procedures and Usage Instructions
1. Installation and Preparation
- Inspect the controller housing, connectors, mounting points, and terminal condition.
- Verify the nameplate and confirm the complete R900958999 identification.
- Mount the unit securely in the control cabinet or approved wall-mounting position.
- Check the hydraulic system, actuator, valve, and feedback transducer specifications.
- Connect the 18–36 V DC power supply using the specified terminals.
- Wire the digital inputs and outputs according to the application diagram.
- Connect the proportional or servo valve control signals.
- Connect position and pressure feedback devices using compatible signal interfaces.
- Install the PROFIBUS DP communication connection and verify bus termination.
- Connect the engineering PC using the appropriate programming cable.
2. Power-On Sequence
- Confirm that hydraulic pressure and mechanical movement are in a safe condition.
- Check the DC supply voltage and polarity.
- Verify protective grounding and signal shielding.
- Switch on the controller power supply.
- Allow the CPU to complete its initialization.
- Check the RUN, CPU, and error indicators.
- Establish communication with the WIN-PED engineering software.
- Verify feedback signals and digital I/O status.
- Check PROFIBUS DP communication with the supervisory PLC.
- Enable hydraulic operation only after confirming that the control system is ready.
3. Normal Operating Procedure
- Load the approved hydraulic axis configuration.
- Verify the connected position transducer and feedback scaling.
- Check valve output polarity and command signal limits.
- Confirm the hydraulic pressure and safety interlocks.
- Execute the approved NC motion program.
- Start with reduced speed and movement limits.
- Verify actual position against the commanded position.
- Monitor pressure, force, and axis response.
- Adjust operating parameters only within approved engineering limits.
- Switch to automatic operation after commissioning checks are complete.
4. Parameter Configuration and Modification
- Connect the PC to the HNC100 programming interface.
- Start the compatible WIN-PED software.
- Establish online communication with the controller.
- Read and back up the existing parameter set before making changes.
- Configure the position controller, pressure controller, or force controller as required.
- Set feedback scaling, zero-point compensation, and signal polarity.
- Configure acceleration, deceleration, travel limits, and position-dependent braking.
- Configure PROFIBUS DP communication parameters to match the PLC.
- Download the approved configuration and verify the controller diagnostics.
- Test the hydraulic axis at reduced speed before restoring normal operation.
5. Shutdown Sequence
- Stop the automatic NC program.
- Command the hydraulic axis to a safe stopping position.
- Reduce the valve command to the approved neutral condition.
- Confirm that actuator movement has stopped.
- Disable hydraulic operation according to the machine procedure.
- Isolate the controller DC supply if maintenance is required.
- Relieve stored hydraulic pressure using the approved hydraulic isolation procedure.
- Verify electrical and hydraulic safety before disconnecting any components.
🔧 Daily Maintenance and Troubleshooting
- Check the RUN and error indicators during operation.
- Inspect power, feedback, and PROFIBUS connectors.
- Check hydraulic hoses, fittings, and valve connections for leakage.
- Monitor position feedback for unstable or inconsistent readings.
- Investigate axis oscillation by checking controller gains and feedback scaling.
- Check pressure overshoot by reviewing pressure feedback and controller settings.
- Investigate communication faults by checking PROFIBUS addressing and termination.
- Back up NC programs and controller parameters regularly.
- Keep the control cabinet clean and maintain appropriate operating temperatures.
⚠️ Safety Precautions
- Commissioning must be performed by qualified hydraulic and automation technicians.
- Never disconnect electrical wiring while the controller is energized.
- Hydraulic systems may retain dangerous pressure after shutdown.
- Secure loads and prevent uncontrolled actuator movement before maintenance.
- Never modify valve output limits without reviewing the hydraulic circuit.
- Do not connect reserved terminals marked for non-use.
- Confirm PROFIBUS compatibility and wiring before powering the system.
- Maintain the original parameter backup before changing control-loop settings.
🔗 Product Keywords and Information
Rexroth R900958999, 090958999, VT-HNC100, VT-HNC100 Digital Axis Controller, Hydraulic Axis Control, Hydraulic Servo Controller, PROFIBUS DP Controller, WIN-PED, Digital NC Control, Hydraulic Motion Control.
For industrial automation and hydraulic control spare parts, visit:
Recommended Bosch Rexroth Models
- VT-HNC100-1-2X/W-08-0-0 – R900955334
- VT-HNC100-1-2X/W-08-I-0 – R900955332
- VT-HNC100-1-2X/W-08-P-0 – R900958999
- VT-HNC100-1-2X/W-08-C-0 – R900959000
- VT-HNC100-2-2X/W-16-P-0 – R900724314
- VT-HNC100-2-2X/W-16-0-0 – R900710116
- VT-HNC100-4-3X/P-I-00/G04 – R901134617
- VT-HNC100-C-3X/P-S-00/000 – R901134618
- VT-HNC100-C-3X/S-S-00/000 – R901112919
- VT-HNC100-1-3X/S-I-30/000 – R901234133
- VT-HNC100DEMO – Hydraulic Control Simulator
- VT-HNC100-2-2X/W-16-C-0 – Verify order number
- VT-HNC100-1-2X/W-08-0-0 – R900955334
- VT-HNC100-1-2X/W-08-I-0 – R900955332
- VT-HNC100-1-2X/W-08-C-0 – R900959000
Note: These models belong to the Rexroth HNC100 hydraulic control family. Communication interfaces, axis counts, I/O configurations, and hardware generations differ. Confirm the complete type code before ordering a replacement.